42
Figure
70
Pressing
the
DOWN
key displays the screen shown in Figure 71. This
screen shows the readings of the four channels dedicated to the CO
2
sensors. The Current reading is either the average of the active
sensors or the lowest active sensor. This reading is the process
control variable for activating the CO
2
valve. The bottom line of this
screen allows the number of sensors to be selected.
Figure
71
To return to the SERVICE MENU, press the
Esc
key.
When the Dehumidifier is purchased with CO
2
control, the Setpoint string of
screens will also include the screens shown in Figure 72. This screen allows
modifying the setpoints for the CO
2
valve. When the CO
2
level rises above
the setpoint plus the differential, the valve will turn off. The valve will turn back
on when the CO
2
level falls below the setpoint. The current valve of the CO
2
sensors is also shown on this screen.
Desert Aire - CM3550 Manual
Содержание CM3550 Series