33
Figure
45
The last screen in the Blower Setup is the Manual Settings,
shown in Figure 46. This screen allows the Blower to be set to
Manual or Automatic Control. In Manual Control, the Manual
Command will set the speed of the Blower.
Figure
46
To return to the Setup Menu, press the
Esc
key.
2.3.3.1.5 Remote Setpoints (Figures 47-52)
Selecting the Remote Setpoints allows for analog inputs 7 and
8 to be set for either 0-10VDC or 4-20mA input values. Analog
Input 7 will vary the temperature setpoint from temperature
values corresponding to the inputs as shown in Figures 49
and 50. Analog Input 8 will vary the RH setpoint from RH
values corresponding to the input as shown in Figures 51 and
52. The bottom line of the screens in Figure 47 and 48 allow
the dehumidifier to use the system setpoints as shown in
Figure 40, or the remote setpoints as defined below.
Desert Aire - CM3550 Manual