background image

4

105056

BLUE-FLAME VENT-FREE PROPANE/LP AND

NATURAL GAS GREENHOUSE CO2 GENERATOR

Continued

 WARNING: If the area in which the CO2 generator may be operated is smaller than that defined as an

unconfined space or if the building is of unusually tight construction, provide adequate combustion and
ventilation air by one of the methods described in the 

National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3,

Canadian Gas Code B-149.1 and 2-M95, Section 7.2 and 7.3, or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR APPLIANCE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install appliance plus any adjoining rooms with doorless passageways or ventilation grills

between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: 

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

  2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

CO2 generator

______________________ Btu/Hr

Gas water heater*

______________________ Btu/Hr

Gas furnace

______________________ Btu/Hr

Vented gas heater

______________________ Btu/Hr

Other gas appliances*

+

______________________ Btu/Hr

Total

=

______________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 5.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 5.

C. Install a lower Btu/Hr appliance, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Example:

Gas water heater

40,000

Btu/Hr

CO2 generator

+

30,000

Btu/Hr

Total

 =

70,000

Btu/Hr

Содержание RN30E-CAN

Страница 1: ...reference BLUE FLAME VENT FREE PROPANE AND NATURAL GAS GREENHOUSE CO2 GENERATOR OWNER S OPERATION AND INSTALLATION MANUAL WARNING This is an unvented gas firedappliance Itusesair oxygen from the spac...

Страница 2: ...plate This appliance is not convertible for use with other gases 2 Do not place propane LP supply tank s inside any structure Locate propane LP supply tank s outdoors 3 If you smell gas shut off gas s...

Страница 3: ...ADEQUATE VENTILATION Unconfined Space Can Gas Code B 149 1 and 2 M95 Section 6 3 3 states An appliance installed for the production of carbon dioxide in a green house may take its combustion air from...

Страница 4: ...ace 50 cu ft 51 2 or 51 200 maximum Btu Hr the space can support 3 Add the Btu Hr of all fuel burning appliances in the space CO2 generator ______________________ Btu Hr Gas water heater _____________...

Страница 5: ...n or Canadian Gas Code B 149 1 and 2 M95 Section 7 2 and 7 3 and or appli cable local codes for required size of venti lation grills or ducts WARNING Rework work sheet adding the space of the adjoinin...

Страница 6: ...ction and service where strong wind gusts from an open door or ventilator can not blow directly into appliance 16 3 4 Figure4 MountingClearancesAsViewed From Front of Appliance INSTALLATION NOTICE A q...

Страница 7: ...d walls do not pop open wings 5 Place mounting bracket onto wall Line up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bracket and into wall anchors 7 Tighten scr...

Страница 8: ...Only Never connect appliance directly to the propane LP supply This appliance requires an external regulator notsupplied Installthe external regulator between the applianceandpropane LPsupply Figure 1...

Страница 9: ...s joints Bubbles form ing show a leak 5 Correct all leaks at once TestPressuresEqualToorLessThan 1 2 PSIG 1 Close manual shutoff valve see Fig ure 14 2 Pressurize supply piping system by ei therusingc...

Страница 10: ...ing Instructions 3 With control knob pressed in strike match Hold match to pilot until pi lot lights 4 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release contro...

Страница 11: ...Figure21showsanincorrectburner flame pattern The incorrect burner flame patternshowsyellowtippingoftheflame It also shows the flame higher than 1 2 the heat shield height Ifburnerflamepatternisincorre...

Страница 12: ...ly open 4 Thermocoupleconnectionlooseatcon trol valve 5 Pilotflamenottouchingthermocouple which allows thermocouple to cool causing pilot flame to go out This problemcouldbecausedbyoneorboth of the fo...

Страница 13: ...ir passageways on appliance blocked 4 Dirtyorpartiallycloggedburnerorifice REMEDY 1 Contact local gas company 2 Clean burner see Cleaning and Main tenance page 11 or replace burner orifice 1 Clean bur...

Страница 14: ...essure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at...

Страница 15: ...nternational s Technical Service Department at 1 800 323 5190 SPECIFICATIONS RP30E CAN RN30E CAN Btu Variable 15 000 30 000 15 000 30 000 Type Gas Propane LP Only Natural Only Ignition Piezo Piezo Pre...

Страница 16: ...UE FLAME VENT FREE PROPANE LP AND NATURAL GAS GREENHOUSE CO2 GENERATOR 1 2 4 5 6 6 7 8 8 9 10 11 12 15 17 19 21 22 23 20 26 25 18 14 16 24 3 13 ODS PILOT 10 1 10 2 ILLUSTRATED PARTS BREAKDOWN RP30E CA...

Страница 17: ...01 Thermocouple 1 10 2 098594 01 Ignitor Electrode 1 11 103447 01 Burner 1 12 099387 05 3 16 Pilot Tubing 1 13 103845 03 Injector L P 1 103845 04 Injector N G 1 14 099066 01 Mounting Bracket 1 15 099...

Страница 18: ...are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installatio...

Отзывы: