Example:

  51,200  Btu/Hr  (maximum  the 

space can support) 

 

 

70,000 Btu/Hr (actual amount of 

Btu/Hr used)

The space in the above example is a confined 

space because the actual Btu/Hr used is more 
than  the  maximum  Btu/Hr  the  space  can  sup-

port. You must provide additional fresh air. Your 
options are as follows:
A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides 
an unconfined space, remove door to adjoin

-

ing  room  or  add  ventilation  grills  between 

rooms.  See 

Ventilation  Air  From  Inside 

Building.

B.  Vent  room  directly  to  the  outdoors.  See 

Ventilation Air From Outdoors

.

C.  Install a lower Btu/Hr fireplace, if lower Btu/

Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support,

 

the space is 

an unconfined space. You will need no additional 

fresh air ventilation.

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus

-

tion and ventilation air shall be 

provided by one of the methods 

described  in  the 

National  Fuel 

Gas Code, ANSI Z223.1/NFPA 54, 

the

 International Fuel Gas Code,

 

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining 
unconfined  space.  When  ventilating  to  an 
adjoining unconfined space, you must provide 
two permanent openings: one within 12" of the 
ceiling and one within 12" of the floor on the 
wall connecting the two spaces (see options 
1 and 2, Figure 2). You can also remove door 
into adjoining room (see option 3, Figure 2). 
Follow  the 

National  Fuel  Gas  Code, ANSI 

Z223.1/NFPA  54,  Air  for  Combustion  and 
Ventilation

  for  required  size  of  ventilation 

grills or ducts.

Ventilation Air From Outdoors

Provide  extra  fresh  air  by  using  ventilation 

grills or ducts. You must provide two perma

-

nent openings: one within 12" of the ceiling 
and one within 12" of the floor. Connect these 

items directly to the outdoors or spaces open 
to the outdoors. These spaces include attics 

and crawl spaces. Follow the 

National Fuel 

Gas  Code,  ANSI  Z223.1/NFPA  54,  Air  for 
Combustion and Ventilation

 for required size 

of ventilation grills or ducts.

IMPORTANT:

  Do  not  provide  openings  for 

inlet or outlet air into attic if attic has a thermo-

stat-controlled power vent. Heated air entering 
the attic will activate the power vent.

AIR FOR COMBUSTION AND VENTILATION

Continued

Figure 3 - Ventilation Air from Outdoors 

(Oxford™ Stove Model Shown)

Figure 2 - Ventilation Air from Inside 

Building (Oxford™ Stove Model Shown)

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

Содержание GXSVYD18NRA

Страница 1: ...do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installa...

Страница 2: ...not prohib ited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases Aftermarket Completion of sa...

Страница 3: ...mfurniture and draperies Do not place clothing or other flammable material on or near the appliance Never place any objects on the heater SAFETY Continued Stove becomes very hot when running heater Ke...

Страница 4: ...SAFETY Continued 11 Do not run heater where flammable liquids or vapors are used or stored under dusty conditions 12 Do not use this stove to cook food or burn paper or other objects 13 Do not use hea...

Страница 5: ...system re quires no matches batteries or other sources to light heater WARNING This heater shall not be installed in a room or space unless the required vol ume of indoor combustion air is provided by...

Страница 6: ...ed a part of the un confined space Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them AIR FOR COMBUSTION AND VENTILATION Continued DETERMINING...

Страница 7: ...ing to an adjoining unconfined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see options 1 and 2 Figur...

Страница 8: ...st point of stove top to any combustible side wall should not be less than 12 B Clearances from outermost point of stove top to any combustible back wall should not be less than 6 includes corner inst...

Страница 9: ...Legs include leg leveler bolts 1 Bottom door 3 Top grates 1 Hardware kit bag with fasteners 5 Carefully lay stove body on back to attach bottom components to stove body see Figure 5 Rest stove on drop...

Страница 10: ...s 13 Remove gas log heater from carton Note Do not pick up gas log heater by the burner itself This could damage heater Always handle the gas log heater by the heater base only 14 Fasten stove pan to...

Страница 11: ...x 1 bolts and washers 6 Place freestanding stove in desired posi tion in room Be sure to maintain clear ances to combustibles as outlined on page 8 CAUTION After installa tion and periodically thereaf...

Страница 12: ...ally tinned copper tubing may be used in certain areas Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of volume will oc...

Страница 13: ...sures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its appliance main gas valve control valve and equip ment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig wi...

Страница 14: ...t which must be lighted by hand When lighting the pi lot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some...

Страница 15: ...nob pressed in for 30 sec onds after lighting pilot After 30 seconds release control knob If control knob does not pop out when released contact a qualified service person or gas supplier for repairs...

Страница 16: ...l burner turns on Hold the control button again until burner turns off see Figure 23 To Lock press both buttons on hand held remote control until light stops flashing Hand held remote control is now l...

Страница 17: ...y debris or rust with no flame present If so turn off heater and let cool Remove blockage Blocked burner flame holes will create soot Pilot Burner Figure 25 Correct Pilot Flame Pattern Propane LP Show...

Страница 18: ...airpassagewaysofheater clean Inspect these areas of heater before each use Have heater inspected yearly by a qualified service person Heater may need more frequent clean ing due to excessive lint from...

Страница 19: ...essure B Dirty or partially clogged ODS pilot 5 Thermocouple connection loose at control valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if p...

Страница 20: ...Clean burner see Cleaning and Maintenance page 18 or replace burner orifice 1 Clean burner see Cleaning and Maintenance page 18 or replace burner orifice 2 Replace damaged burner 3 Replace gas contro...

Страница 21: ...lot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page REM...

Страница 22: ...www desatech com 113084 01J 22 Parts Models SVYD18PRA and svyd18nrA 17 17 18 19 24 15 14 16 13 12 12 11 22 23 20 10 9 21 4 8 5 3 2 21 7 6 1...

Страница 23: ...e 1 099387 15 Pilot Tube 1 10 103781 02 Gas Control Valve 1 103781 01 Gas Control Valve 1 11 103345 02 Lower Bracket 1 12 M11084 38 Screw 8 x 0 38 7 13 Painted Base Assembly 1 14 098271 10 Ignitor Cab...

Страница 24: ...m 113084 01J 24 2 5 5 5 5 8 7 4 6 7 1 7 2 4 9 7 3 3 1R 1C 1L 10 9 10 Parts Oxford VCIS Series and PVCIS Series Victor Hearth VH A Series Indicates Color Suffix Designation Oxford Stove Body Victor Hea...

Страница 25: ...uts 1 Per Unit 1 7 3 Bottom Floor Bolts M6 x 1 25 mm Long With Flat Washer And Lock Washer 4 Per Unit 1 7 4 Leg Bolts M8 x 1 25 20 mm Long With Flat Washer And Lock Washer 4 Per Unit 1 8 104178 01 Bac...

Страница 26: ...ting LLC have ready your name your address model and serial numbers of your heater how heater was malfunctioning purchase date Usually we will ask you to return the part to the factory Parts Not Under...

Страница 27: ...log heater to be turned on and off with a wall switch Cleaning Kit Cck For all models Your vent free gas appliance requires regular cleaning and maintenance to prevent performance problems This kit gi...

Страница 28: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Отзывы: