1 2 - 2 D O U B L E V O LT A G E
A
W ARNING
ELECTRIC SHOCK can kill.
■ Do not touch the circuit inside the machine during
operation to prevent decease due to electric shock.
* When open the control pane) or the like for changing
the output voltage, turn OFF the breaker and stop the
machine in advance.
(1) Description
T he machine is designed with double voltage specification, which allows the output
■
■'voltage of 200 V class or 400 V class to be selected with the voltage change over cables. -
(2) Method for selecting output voltage
The machine is shipped from the plant with its output voltage normally set at 200/220V
unless otherw ise specified.
Therefore, select the output the voltage required for work in accordance with the
procedure described following :
m
x
у
z
400V class
U
V
w
4
У «г
о
vo к »
1
1 I I
X Y Z
200V class
-
88
-