Installation procedure
* Install the machine horizontally on a solid foundation.
* Provide a space of more than about lm at the side of the control panel and fuel feed port
to ensure correct operation and supply.
* Provide a space of more than about 1.2m on the left and right sides for check of the
engine, oil supply and cable connection work.
* A sufficient space is required at the top of the machine to allow hot air (exhaust air)
from the radiator and exhaust gases to be discharged and to supply w ater to the radiator.
* When the machine is operated in a place with much dust or salt, careful maintenance is
required to prevent clogging or damage to the radiator or poor insulation of electric parts.
Indoor installation
* Exhaust gases should be discharged outdoors using an exhaust pipe.
* Exhaust air should also be discharged outdoors using a duct or the like.
*
Insufficient indoor ventilation will raise the (indoor) tem perature and
affects the performance of the machine.
* For details of required volume of ventilation, contact distributor or our office.
-