Modbus
Offset
Register
Description
50304
(PS24 only)
10303
CT3 Voltage Source
Voltage source = Select voltage phase to associate
with CT for power and energy calculations. 0= not
used,1=L1, 2=L2, 3=L3,4=L1-L2,5=L3-L2, 6=L1-L3,
default=L1. Note this register is only active if Service
Type (44607) is set to 2 (Single/Independent)
50305
(PS24 only)
10304
CT3 Amps Multiplier
Amps multiplier= Multiply amps value by this scalar.
For use with 5A CTs and single leg monitoring of a
three phase load. Affects all parameters that use
amps (e.g., kW). Whole numbers only.
50325
10324
CT3 Type
Select 1=mV or 2=Rogowski CT3s
50399
10398
CT3 Phase Shift
Phase Shift X 100 +/-
P
ULSE
O
UTPUT
/I
NPUT
R
EGISTERS
Modbus
Offset
Register
Description
44400
(PS24 only)
4399
I/O port 1 status
0 = input LOW (switch is closed)
1 = input HIGH (switch is open)
44401
(PS24 only)
4400
I/O port 2 status
0 = input LOW (switch is closed)
1 = input HIGH (switch is open)
44402
(PS3 only)
4401
Port 1 output control when
used as an on/off—open/closed
switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45110 must = 0 to use
44403
(PS3 only)
4402
Port 2 output control when
used as an on/off—open/closed
switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45210 must = 0 to use
45100
(PS24 only)
5099
Configures the pulse input for
I/O port 1
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling
edges are ignored. If pulse output is enabled, it is
disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising
edges are ignored. If pulse output is enabled, it is
disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse
output is enabled, it is disabled when this
configuration is set. (Note when pulse is off, I/O
control is enabled)
Setting this register to a value other than 0, forces
register 45110 to 0.
45101
(PS24 only)
5100
I/O port 1 pulse input
accumulator LSW
Scaled pulse LSW
45102
(PS24 only)
5101
I/O port 1 pulse input
accumulator MSW
Scaled pulse MSW
67