Modbus
Register
Offset
Register Name
Detailed Description
44401
4400
I/O port 2 status
0 = input LOW (switch is closed)
1 = input HIGH (switch is open)
45200
5199
Configures the pulse input for I/O
port 2
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling
edges are ignored. If pulse output is enabled, it is
disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising
edges are irnored. If pulse output is enabled, it is
disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse
output is enabled, it is disabled when this
configuration is set. (Note when pulse is off, I/O
control is enabled)
Setting this register to a value other than 0, forces
register 45210 to 0.
45201
5200
I/O port 2 pulse input
accumulator LSW
Scaled pulse LSW
45202
5201
I/O port 2 pulse input
accumulator MSW
Scaled pulse MSW
45203
5202
I/O port 2 pulse input scaling
(integer)
Integer scale factor
(Scale = 45203 + 45204/1000)
45204
5203
I/O port 2 pulse input scaling
(decimal)
x1000 decimal fraction of scale factor
Table F-7: Modbus Port 2 Pulse Input
98