Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-00-11
LOCAL / REMOTE Selection
Factory Setting: 0
Settings 0: Standard HOA function
1: Switching Local / Remote, the drive stops
2: Switching Local / Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Switching Local / Remote, the drive runs as the LOCAL setting for
frequency and operation status
4: Switching Local / Remote, the drive runs as LOCAL setting when switch to
Local and runs as REMOTE setting when switch to Remote for frequency
and operation status.
AUTO / HAND mode can be selected or switched by using digital keypad KPC-CC01 (optional)
or setting multi-function input terminal MI = 41, 42.
The factory setting of Pr. 00-29 is 0 (standard Hand-Off-Auto function). The AUTO frequency and
source of operation can be set by Pr. 00-20 and Pr. 00-21, and the HAND frequency and source
of operation can be set by Pr. 00-30 and Pr. 00-31.
When external terminal (MI) is set to 41 and 42 (AUTO / HAND mode), the settings of Pr. 00-29 =
1,2,3,4 will be disabled. The external terminal has the highest priority of command, and Pr. 00-29
will function as standard HOA mode.
When Pr. 00-29 is not set to 0, Local / Remote function is enabled, the top right corner of digital
keypad KPC-CC01 (optional) will display “LOC” or “REM”. The LOCAL frequency and source of
operation can be set by Pr. 00-20 and Pr. 00-21, and the REMOTE frequency and source of
operation can be set by Pr. 00-30 and Pr. 00-31. LOC / REM mode can be selected or switched
by using digital keypad KPC-CC01 (optional) or setting multi-function input terminal MI = 56. The
AUTO key of the digital keypad is for the REMOTE function, and HAND key is for the LOCAL
function.
When external terminal (MI) is set to 56 for LOC / REM mode selection, if Pr. 00-29 is set to 0,
then the external terminal function is disabled.
When external terminal (MI) is set to 56 for LOC / REM mode selection, if Pr. 00-29 is not set to 0,
then AUTO / HAND key will be disabled, and the external terminal has the highest priority of
command.
Source of the Master Frequency Command (HAND)
Factory Setting: 0
Settings 0: Digital keypad
1: Communication RS-485 input
2: External analog input (Refer to Pr. 03-00)
3: External UP / DOWN terminal
6: CANopen communication card
7: Digital keypad dial
8: Communication card (not includes CANopen card)
[Note]: Need to use with MO setting as 41, or use with KPC-CC01
It is used to set the source of the master frequency in HAND mode.
Содержание VFD11AMS21AFSHA
Страница 5: ...IV This page intentionally left blank...
Страница 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Страница 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Страница 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Страница 22: ...Chapter 4 Wiring MS300 High Speed Model 4 1 Chapter 4 Wiring 4 1 Wiring 4 2 System Wiring Diagram...
Страница 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Страница 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Страница 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Страница 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Страница 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Страница 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Страница 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Страница 204: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 3 Diagram 03 Diagram 04 Diagram 05...
Страница 205: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 4 Diagram 06 Diagram 07 Diagram 08...
Страница 206: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 5 Diagram 09 Diagram 10 Diagram 11...
Страница 207: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 6 Diagram 12 Diagram 13 Diagram 14...
Страница 208: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 7 Diagram 15 Diagram 16 Diagram 17...
Страница 209: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 8 Diagram 18 Diagram 19 Diagram 20...
Страница 210: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 9 Diagram 21 Diagram 22 Diagram 23...
Страница 211: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 10 Diagram 24 Diagram 25 Diagram 26...
Страница 212: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 11 Diagram 27 Diagram 28 Diagram 29...
Страница 213: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 03 12 Diagram 30 Diagram 31 Diagram 32...
Страница 287: ...Chapter 12 Description of Parameter Settings MS300 High Speed Model 12 14 7 This page intentionally left blank...
Страница 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Страница 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...