3
10cm
10cm
5cm
5cm
5cm
10cm
10cm
10cm
13.5cm
8cm
Connections:
Installations intended to meet UL and CUL requirements must follow the instructions
provided in “Wiring Notes” section below as a minimum standard. Where local codes
exceed these requirements, they must also be followed. Refer to the technical data label
affixed to the AC drive and the motor nameplate for electrical data.
Basic Wiring Diagram
Users must connect wiring according to the following circuit diagram shown below.
L/L1
N/L2
U/T1
V/T2
W/T3
IM
RS-485 Serial Interface
1
EV
2 GND
3 SG
4 SG+
PIN 1 & 2 are the power source for
the digital keypad and should not
be used while using RS-485
communication.
:+
:
:
-
:
FWD/REV
RUN/STOP
Digital Signal
Common Terminal
Fault Output
(Open Collector)
Wire Gauge: 22-14 AWG
Torque: 10kgf-cm
(8.7 in-lbf)
*NOTE*:
Do not plug a Modem or telephone line to the RS-485 communication port,
permanent damage may result. Terminals 2 & 5 are the power sources for the
optional copy keypad and should not be used while using RS-485
communication.