Troubleshooting and Fault Information 

The AC drive has a comprehensive fault diagnostic system that includes several different 
alarms and fault message. Once a fault is detected, the corresponding protective functions 
will be activated to shut down the AC drive output. Below are the fault descriptions, for a 
fault shown on the AC drive digital keypad. After fault has been cleared, switch the 
Run/Stop key to stop mode to reset the drive. 
 

Fault Display 

Fault Descriptions

Corrective Actions 

Alarm LED lighten after 

power on 

Hardware failure 

Return to the factory 

Alarm LED flashes once 

in every two seconds 

The AC drive 

detects an 

abnormal increase 

in current   

(Over-current) 

1. Increase the acceleration time 

2. Check whether the motor output power 

corresponds to the AC drive output 

power 

3. Check the wiring connection between the 

AC drive and motor for possible short 

circuit 

4. Check for possible over loading 

conditions at the motor 

Alarm LED flashes twice 

in every two seconds 

(Over-voltage)  

The AC drive 

detects that the 

DC-BUS voltage 

has exceeded its 

maximum 

allowable value 

1. Check whether the input voltage falls 

within the rated AC Drive input voltage. 

2. Check for possible voltage transients.   

3. Bus over-voltage may be caused by 

motor regeneration, increase the 

accel/decel time. 

Alarm LED flash thrice in 

every two seconds 

(Overload) 

Motor overload   

1. Check for possible motor overload. 

2. Adjust torque detection setting of the DIP 

SW4 to an appropriate setting. 

3. Increase the AC Drive’s output capacity. 

Alarm LED flashes four 

times in every two 

seconds 

(Over-heating) 

The AC drive 

temperature 

sensor detects 

excessive heat.   

1. Ensure that the ambient temperature 

falls within the specified temperature 

range. 

2. Make sure that the ventilation holes are 

not obstructed. 

3. Provide enough spacing for adequate 

ventilation. 

Alarm LED flashes five 

times in every two 

seconds 

(Low voltage) 

The AC drive 

detects that the 

DC Bus Voltage 

has fallen below 

its minimum value.

Check whether the input voltage falls within 

the rated AC Drive input voltage. 

Alarm LED flashes 

Change DIP SW 

while drive is 

running 

Switch the Run/Stop key to Stop mode to 

reset the AC drive. 

Содержание VFD-L

Страница 1: ...IWAN TEL 886 3 362 6301 FAX 886 3 362 7267 http www deltaww com acdrives NORTH SOUTH AMERICA DELTA PRODUCTS CORPORATION Sales Office P O BOX 12173 5101 DAVIS DRIVE RTP NC 27709 U S A TEL 1 919 767 381...

Страница 2: ...001L21A INPUT 1PH 200 240V 50 60Hz 1 4A OUTPUT 3PH 0 240V 0 8A 303VA 100W Freq Range 1 00 120 00Hz DELTA ELECTRONICS INC MADE IN XXXXXX 001L21AT001007 AC Drive Model Input Spec Output Spec Output Freq...

Страница 3: ...e conduit trucking High voltage insulation test equipment must not be used on cables connected to the drive Wait five minutes for DC bus capacitors discharge Any Electrical or mechanical modification...

Страница 4: ...must connect wiring according to the following circuit diagram shown below L L1 N L2 U T1 V T2 W T3 IM RS 485 Serial Interface 1 EV 2 GND 3 SG 4 SG PIN 1 2 are the power source for the digital keypad...

Страница 5: ...starts operation when closes M1 FWD REV Normally Open contact AC drive starts reverse motion when closes MO1 Fault Indication When error is detected MO1 will close RS 485 Serial Communication Port Whe...

Страница 6: ...ON 1 2 3 4 5 6 7 Reverse disable ON 1 2 3 4 5 6 7 Low torque output 4 Torque Setting ON 1 2 3 4 5 6 7 High torque output ON 1 2 3 4 5 6 7 Applicable for 40 100W motor 5 Electronic Thermal Setting ON...

Страница 7: ...Switch pins 1 to 6 Refer to the description of setting up address VFD L type Communication agreement Modbus ASCII mode protocol 7 N 2 Baud rate 9600 The computer then controls each AC Drive according...

Страница 8: ...s n 25 maximum of 50 ASCII codes LRC CHK 1 LRC CHK 0 LRC check sum 8 bit check sum consists of 2 ASCII codes END 1 End characters END1 CR 0DH END0 LF 0AH END 0 ADR Communication Address Valid communic...

Страница 9: ...CHK 0 1 CR CR CR CR END 1 END 0 LF END 1 END 0 LF END 1 END 0 LF END 1 END 0 LF CHK check sum LRC Longitudinal Redundancy Check is calculated by summing up the values of the bytes from ADR1 to last da...

Страница 10: ...e 1 Low Torque 1 Read Write 7 Electronic Thermal 0 25 60 w 1 40 100 w 1 Read Write 8 Communication Addresses 01 to 63 1 Read Write 9 Software Version Read only Read Only Address List The contents of a...

Страница 11: ...ure cF3 3 26 Hardware failure cF3 5 current detection 30 Hardware failure hpf 2 31 Hardware failure hpf 3 Bit 0 to 1 00 STOP 01 Ramp stop 10 Zero speed 11 Operation Bit 2 Reserved Bit 3 to 4 00 Forwar...

Страница 12: ...dition that caused the exception is returned An example of exception response of command code 06H and exception code 02H STX 3AH 0 30H ADDRESS 1 ADDRESS 0 1 31H FUNCTION CMD 1 8 38H FUNCTION CMD 0 6 3...

Страница 13: ...Voltmeter Periodic Maintenance It is necessary to stop the motor operation during the check up 1 Tighten and reinforce the screws of the AC drive if necessary cause it may loose due to the vibration o...

Страница 14: ...nds Over voltage The AC drive detects that the DC BUS voltage has exceeded its maximum allowable value 1 Check whether the input voltage falls within the rated AC Drive input voltage 2 Check for possi...

Страница 15: ...Systems SVPWM Space Vector Pulse Width Modulation carrier frequency 10kHz Torque Setting High Low Switching Overload Endurance 150 of rated current for 1 minute Accel Decel Time 0 05 to 30 0 seconds C...

Страница 16: ...VFD001L21A VFD40WL11A VFD40WL21A W T3 N L2 V T2 U T1 L L1 Unit mm inch 145 1 5 71 2 7 0 11 8 0 0 31 VFD001L11B VFD001L21B 52 5 2 07 VFD40WL11B VFD40WL21B 155 7 6 13 60 0 2 36 H ig h S T O P F W D 100...

Отзывы: