B. About other problems that might happen:

No.

Problem

Possible Cause

Solution

1

Overload

The UPS is 

overloaded.

Decrease your 

connected loads.

2

Battery Missing

Internal battery cables 

are not connected or 

not firmly connected.

1. Please contact service 

personnel.

2. Connect the internal 

battery cables and 

connect them firmly.

3

Weak Battery/ 

Battery 

Replacement

The batteries are 

damaged or battery 

lifetime is due.

Please contact service 

personnel.

4

Abnormal Input 

(when the AC icon 

 is flashing)

The AC input voltage 

or frequency is out 

of the acceptable 

bypass range.

1. Check if the AC input 

voltage or frequency is 

abnormal.

2. Please contact service 

personnel.

NOTE: 

If all possible causes are eliminated but the alarm still appears, please 

contact your local dealer or customer service.

9

Optional Accessories

No.

Item

Function

1

Mini SNMP Card

Monitors and controls the status of the UPS 

via a network system.

2

Mini Relay I/O Card

Increases the quantity of dry contacts.

3

Mini MODBUS Card

Lets the UPS have MODBUS communication 

function.

4

Cable & Wire Mount 

Assembly

Fastens an IEC output cable to prevent the 

cable from coming off.

5

Tower Stands

Sustain the UPS vertically.

6

Rail Kit

Fixes the UPS in a rack cabinet firmly.

NOTE: 

For more details, please contact your local dealer or customer 

service.

10

Technical Specifications

Model

R-1K

R-2K

R-3K

Power Rating

1kVA/0.9kW

2kVA/1.8kW

3kVA/2.7kW

Waveform

Pure Sine Wave

Input

Nominal 

Voltage

200

*

1

/208

*

1

/220/230/240 Vac

Voltage Range

175 ~ 280 Vac (100% load);  

80 ~ 175 Vac (50% ~ 100% load)

Frequency

50/60 Hz (± 10 Hz)

Power Factor

> 0.99 (full load)

Input

iTHD

< 3%

Output

Power Factor

0.9

Voltage

200

*

1

/208

*

1

/220/230/240 Vac

Voltage 

Regulation

± 1% (linear load)

Frequency

50/60 Hz (± 0.05 Hz)

Output

vTHD

< 3% (linear load)

Overload 

Capability

< 105%: continuous; 105% ~ 125%: 1 minute; 

125% ~ 150%: 30 seconds

Cress Factor

3 : 1

Connection 

Suffix B0B1

IEC C13 x 4

IEC C13 x 6 

 IEC C19 x 1

IEC C13 x 6 

 IEC C19 x 1

Connection 

Suffix B1B1

Brazilian

socket x 3

Brazilian socket x 4

Connection 

Suffix B0B2

Argentinian

socket x 3

Argentinian socket x 4

Efficiency

On-line Mode

91%

Up to 93%

Model

R-1K

R-2K

R-3K

Battery

Battery Voltage

24 Vdc

48 Vdc

72 Vdc

Backup Time

*

2

 

(Internal 

Batteries Only) 

6.5 minutes

7 minutes

7 minutes

Recharge Time

(Internal 

Batteries Only) 

3 hours to 90%

Charge Current

1.5A

Audible Noise*

3

< 40 dBA

< 43 dBA

< 43 dBA

Display

LED indicators & LCD display

Communication Interfaces

MINI Slot x 1, RS-232 Port x 1, USB Port x 1

Physical

Dimensions

(W × D × H )

440 x 335 x 

88 mm

440 x 430 x 

88 mm

440 x 565 x 

88 mm

Weight

11.5 kg

20.6 kg

27.5 kg

Environment

Operating 

Altitude

1000 meters (without derating)

Operating 

Temperature

0 ~ 50°C

*

4

Relative 

Humidity

5% ~ 95% (non-condensing)

NOTE: 

1. 

*

1

  When the UPS is de-rated to 90% of its capacity.

2. 

*

2

  When the total load of the UPS reaches 75%.

3. 

*

3

  If the UPS is runnning in room temperature and below 75% load  

capacity.

4.  

*

4

 When the operating temperature is at 40~50°C, the UPS will be de-

rated to 80% of its capacity.

5.  Please refer to the rating label for the safety rating.

6.  All specifications are subject to change without prior notice.

Содержание UPS102R2000B0B1

Страница 1: ...disconnect the AC input power and ensure the UPS is powered off otherwise hazardous voltage may still exist at the output receptacles of the UPS which presents a possible risk of current leakage 7 Pl...

Страница 2: ...he dealer z z UPS102 202 302R2000B0B1 4 4 4 2 Delta UPS Amplon Family R Series Single Phase 1 2 3 kVA Installation Operation Quick Guide ENGLISH 1 3 4 2 6 5 ON OFF SETUP No Item Q ty 1K 2 3K 1 UPS 1 P...

Страница 3: ...ates the UPS 4 Input Breaker Prevents the UPS from damage caused by high current and protects the utility power from further damage when the UPS fails 5 AC Input Input Socket Connects the UPS to the m...

Страница 4: ...hear one beep z z Battery Test Only applicable for on line mode Press and hold the button for 3 seconds and the UPS will transfer to run in battery mode to perform a battery test After the battery tes...

Страница 5: ...rings of the Delta external battery pack s Only use the parameters of the Delta external battery pack s for the battery setting but not those of the UPS s internal batteries If the parameters of the D...

Страница 6: ...the UPS is operating in standby mode ECO On line Mode Graph Illuminates when the UPS is operating in on line mode ECO Battery Mode Graph Illuminates when the UPS is operating in battery mode ECO ECO M...

Страница 7: ...k s to the UPS 1 Verify if the UPS s input cord meets with N L G of the wall socket 2 Plug the UPS s input cord into the wall socket 3 Press and hold the ON button for 3 seconds and release it after y...

Страница 8: ...vice 10 Technical Specifications Model R 1K R 2K R 3K Power Rating 1kVA 0 9kW 2kVA 1 8kW 3kVA 2 7kW Waveform Pure Sine Wave Input Nominal Voltage 200 1 208 1 220 230 240 Vac Voltage Range 175 280 Vac...

Отзывы: