background image

www.deltapowersolutions.com

6 / 8

NOTE: 

Please read the columns A, B and C together to understand the LCD 

information, such as input voltage, estimated remaining backup time, etc.

Column A 

Meaning

Column C 

Meaning

The 7-segment  

display shows  

readings or words.

AH

Ampere hour

Column B

Meaning

V

Voltage

SET

Setup mode

%

Percentage

IN

Input

Hz

Frequency

OUT

Output

KVA

kVA

BATT

Battery

KW

kW

LOAD

Load

MIN

Minute

TEST

Test

°C

The UPS’s internal 

temperature

6.5  16-segment Display

Hz
KW

KVA

AH

MIN

MIN

ECO

V

V%

IN

SET IN OUT BATT

RUN TIME

°C

LOAD TEST

Display

Meaning

The 16-segment display shows numbers or error codes.

IN

Input

RUN TIME

Estimated remaining backup time.

V

Voltage

MIN

Minute

NOTE: 
*

1

 

In standby mode or in bypass mode, if you change the '

AST

' setting 

from '

OFF

' to '

ON

' and execute the step

5

 to confirm such change, 

the UPS will exit from the setup mode and run in '

Auto-Start to On-line

mode right away.

6.3  LCD Display

Hz
KW

KVA

AH

MIN

MIN

ECO

V

V%

IN

SET IN OUT BATT

RUN TIME

°C

LOAD TEST

Icon(s)

Naming

Description

AC Icon

Indicates the input power status.
1. 

ON

: Within the acceptable bypass range.

2. 

Flashing

: Out of the acceptable bypass 

range but sufficient to let the UPS operate 

 

in on-line mode.

3. 

OFF

: Out of the acceptable bypass range 

and not sufficient to let the UPS operate in 

on-line mode.

Output Icon

Indicates the output status.
1. 

ON

: There is output.

2. 

OFF

: There is no output.

Battery Power 

Icon

Indicates the battery power status.
1. 

ON

: The battery power is on.

2. 

OFF

: The output is not supplied by the 

batteries.

ECO

Standby Mode 

Graph

Illuminates when the UPS is operating in 

standby mode.

ECO

On-line Mode 

Graph

Illuminates when the UPS is operating in  

on-line mode.

ECO

Battery Mode 

Graph

Illuminates when the UPS is operating in 

battery mode.

ECO

ECO Mode 

Graph

Illuminates when the UPS is operating in  

ECO mode.

ECO

Frequency 

Converter 

Mode

Illuminates when the UPS is operating in 

frequency converter mode (the icon 

ECO

  

will flash while these two icons 

 & 

remain on).

Icon(s)

Naming

Description

ECO

Bypass Mode 

Graph

Illuminates when the UPS is operating in bypass 

mode.

ECO Mode

Illuminates when the UPS is operating in ECO 

mode.
1. 

ON

: ECO function is enabled and the 

connected loads are fed by the utility AC power.

2. 

Flashing

: ECO function is enabled and 

the connected loads are fed by the double 

conversion.

Buzzer Off 

Icon

Illuminates when the buzzer is disabled.

Load Level 

Bar Graph

Indicates the load level status.

ON

: load level (%) 

*

1

.

NOTE:

 When the UPS is overloaded, 

the warning icon 

 will flash and the 

7-segment display will flash with a load 

level value.

Battery Level 

Bar Graph

Indicates the battery level status.

1. 

ON 

( ): The remaining battery capacity (%) 

*

1

.

2. 

Flashing 

( ): Low battery.

3. 

Flashing 

Hz
KW

KVA

AH

MIN

V

%

SET IN OUT BATT

°C

LOAD

TEST

 ): There is no battery or battery 

replacement is required 

*

2

.

NOTE: 

1. 

*

1

  means that:

1%~25%: the 1st segment will illuminate.

26%~50%: the first two segments will illuminate.
51%~75%: the first three segments will illuminate.

76%~100%: all segments will illuminate.

2.  

*

2

 If you need to replace the batteries or the Delta external battery pack(s), 

please contact service personnel.

6.4  7-segment Display

Hz
KW

KVA

AH

MIN

MIN

ECO

V

V%

IN

SET IN OUT BATT

RUN TIME

°C

LOAD TEST

Hz
KW

KVA

AH

MIN

MIN

ECO

V

V%

SET IN OUT BATT

°C

LOAD TEST

7-segment Display

Column A Column C

Column B

Continue to the Next Page

 



Содержание UPS102R2000B0B1

Страница 1: ...disconnect the AC input power and ensure the UPS is powered off otherwise hazardous voltage may still exist at the output receptacles of the UPS which presents a possible risk of current leakage 7 Pl...

Страница 2: ...he dealer z z UPS102 202 302R2000B0B1 4 4 4 2 Delta UPS Amplon Family R Series Single Phase 1 2 3 kVA Installation Operation Quick Guide ENGLISH 1 3 4 2 6 5 ON OFF SETUP No Item Q ty 1K 2 3K 1 UPS 1 P...

Страница 3: ...ates the UPS 4 Input Breaker Prevents the UPS from damage caused by high current and protects the utility power from further damage when the UPS fails 5 AC Input Input Socket Connects the UPS to the m...

Страница 4: ...hear one beep z z Battery Test Only applicable for on line mode Press and hold the button for 3 seconds and the UPS will transfer to run in battery mode to perform a battery test After the battery tes...

Страница 5: ...rings of the Delta external battery pack s Only use the parameters of the Delta external battery pack s for the battery setting but not those of the UPS s internal batteries If the parameters of the D...

Страница 6: ...the UPS is operating in standby mode ECO On line Mode Graph Illuminates when the UPS is operating in on line mode ECO Battery Mode Graph Illuminates when the UPS is operating in battery mode ECO ECO M...

Страница 7: ...k s to the UPS 1 Verify if the UPS s input cord meets with N L G of the wall socket 2 Plug the UPS s input cord into the wall socket 3 Press and hold the ON button for 3 seconds and release it after y...

Страница 8: ...vice 10 Technical Specifications Model R 1K R 2K R 3K Power Rating 1kVA 0 9kW 2kVA 1 8kW 3kVA 2 7kW Waveform Pure Sine Wave Input Nominal Voltage 200 1 208 1 220 230 240 Vac Voltage Range 175 280 Vac...

Отзывы: