113
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
8.5.4 Constant cos phi (cos φ)
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
This function allows you to set a constant cos φ.
Setting options
Parameter
Description
Setting range
Mode
Switch the function on and off.
ON
|
OFF
Cos Phi
Constant cos phi (cos φ), capacitive or inductive
0.80 .. 0.99 cap
1
0.80 .. 0.99 ind
Menu item path
Main Menu
>
Active/Reactive Pwr
>
Reactive Power Ctrl
>
Constant cosphi
Calling up the menu item
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Active/Reactive Pwr
entry and then press
the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Reactive Power Ctrl
Active Power Ctrl
4.
Use the
and
buttons to select the
Reactive Power Ctrl
entry and then press
the
ENT
button.
Q(V)
Constant Q
Cos phi (P)
Constant cos phi
5.
Use the
and
buttons to select the
Constant cos phi
entry and then press the
ENT
button.