8 Settings
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
102
8.4.9 AC connection
Overview
The inverter is configured by default for an AC connection with
3-phases and a neutral conductor (
3P4W
). If you wish to connect
the inverter without a neutral conductor then you must set the AC
connection type to
3P3W
after commissioning.
Setting options
Parameter
Description
Setting range
AC connection
Set the AC connection type.
3P3W
: 3-phase system
without
a neutral conductor (L1, L2, L3, PE)
3P4W
: 3-phase system
with
a neutral conductor (L1, L2, L3, N, PE)
3P3W | 3P4W
Menu item path
Main Menu > Install Settings > AC connection
Setting the AC connection type
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry and then press the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
AC Connection: 3P3W
EPO: Normal Close
Anti-islanding: ON
Max. Power: 100%
Return to Factory
4.
Use the buttons
and
to select the entry
AC connection
and press the
ENT
but-
ton.
→ The shape of the arrow changes , the value can be changed.
The currently set value is displayed after the entry.
5.
Use the
and
buttons to configure the value and then press the
ENT
button.