109
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
Setting options
Parameter
Description
Setting range
Mode
Switch the function on and off.
ON
|
OFF
F Start
The grid frequency above which the active power being fed is
reduced
.
50.00 .. 55.00 Hz
F Restart
The grid frequency below which the active power being fed is
reduced
.
50.00 .. 55.00 Hz
Gradient
When the grid frequency exceeds
F Start
the active power being
fed is continuously reduced by the value specified here.
0 .. 100%
T Restart
When the grid frequency falls below
F Restart
again, the inverter
waits for the time specified here before removing the previously
imposed reduction of fed active power.
0 .. 600 s
Menu item path
Main Menu
>
Active/Reactive Pwr
>
Active Power Ctrl
>
Power vs. Frequency
Calling up the menu item
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1.
If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Active/Reactive Pwr
entry and then press
the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Reactive Power Ctrl
Active Power Ctrl
4.
Use the
and
buttons to select the
Active Power Ctrl
entry and then press the
ENT
button.
P(V)
Power vs. Frequency
Power Limit
5.
Use the
and
buttons to select the
Power vs. Frequency
entry and then press
the
ENT
button.