4-11
4
ௐ ௐ
Communication Interfaces
No.
Event
Description
1
None
No set-up.
2
Generator Status
Generator status detection.
3
Battery Ground Fail
Battery leakage detection.
4
External Battery Breaker
Detection
Status detection of the external battery cabinet’s
breaker or switch.
4.1.7 Parallel Communication Cards
The UPS has two parallel communication cards, which are master parallel communication
card and backup parallel communication card. Each card has one LED indicator. Please see
Figure 4-11
for their location.
If both cards work normally, the master parallel communication card’s LED indicator will
illuminate green and the backup parallel communication card’s LED indicator will illuminate
yellow.
If one card works normally and the other works abnormally, the normal card’s LED indicator
will illuminate green and the abnormal card’s LED indicator will illuminate red.
During initialization process, both cards’ LED indicators flash yellow.
DISPLAY
REPO
NC NO
EXT. BATT
TEMP.
BT1 BT2
EXT.SWITCH
STATUS
S1
S2
S3
S4
BT3 BT4
O/P DRY
CONTACT
USB
RS-232
P1
P2
P3
P4
P5
P6
I/P DRY
CONTACT
P1
P2
BATT.
START
BATT.
START
P3
P4
PARALLEL
PARALLEL
Master Parallel Communication Card’s
LED Indicator
Master Parallel
Communication Card
Backup Parallel Communication Card’s
LED Indicator
Backup Parallel
Communication Card
(Figure 4-11: Location of Parallel Communication Cards and Their LED Indicators)
4.1.8 Parallel Ports
The parallel ports are used to connect parallel UPSs to increase the system capacity and
redundancy. With the provided parallel cable, up to eight UPS units with the same capacity,
voltage and frequency can be paralleled. To enhance parallel reliability, please adopt Daisy
Chain method (see
Figure 5-41
&
Figure 5-43
) to execute parallel configuration.
WARNING:
The provided parallel cable is placed in the accessory package. Using other types
of cables to connect the parallel UPSs may cause parallel failure, malfunctions and
accidents.
Содержание Modulon DPH 200kVA
Страница 26: ...2 14 Modulon DPH Series...
Страница 62: ...3 36 Modulon DPH Series...
Страница 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 213: ...9 1 9 Maintenance Maintenance 9...
Страница 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Страница 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Страница 228: ...A1 4 Modulon DPH Series...
Страница 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 231: ......
Страница 232: ...5013255601...