3-10
Modulon DPH Series
3.1.8 Energy Recycle Mode _ Single Input_ Single Unit
127(
Energy recycle mode is only applicable to single input and single unit
application.
Energy recycle mode is only applicable to UPS self-test only. Without connection of any
critical loads, the UPS can execute current test under full load condition. Before you activate
energy recycle mode, please make sure that the Delta or non-Delta external maintenance
bypass cabinet’s Manual Bypass Breaker or Switch (Q3), Output Breaker or Switch (Q4) and
each external battery cabinet’s battery breaker (Q5) are in the
OFF
status.
To activate energy recycle mode (only qualified service personnel can do so), please refer
to
6.2.8 Energy Recycle Mode Start-up Procedures
,
7.6 Main Screen
and
7.10.2 Mode
Setting
.
For the diagram of energy recycle mode, please see
Figure 3-10
. During energy recycle
mode, the UPS’s tri-color LED illuminates yellow and the text
‘Energy Recycle’
appears in
the upper right corner of the screen.
MAIN
LOAD
Q1
Q0
Q4
Q3
UPS
Q5
Rectifier
Inverter
Static Switch
Delta or non-Delta External Maintenance Bypass Cabinet
Batteries
(Figure 3-10: Energy Recycle Mode Diagram_ Single Input Single Unit)
Содержание Modulon DPH 200kVA
Страница 26: ...2 14 Modulon DPH Series...
Страница 62: ...3 36 Modulon DPH Series...
Страница 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 213: ...9 1 9 Maintenance Maintenance 9...
Страница 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Страница 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Страница 228: ...A1 4 Modulon DPH Series...
Страница 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 231: ......
Страница 232: ...5013255601...