7-15
7
ௐ ௐ
LCD Display & Settings
7
Frequency
Conversion
MEASUREMENT
MAINTENANCE
EVENT LOG
LOG IN
Administrator
Power Flow
UPS-1.1
SETUP
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
Power Flow
Summary
System Status
10:15
May 25,2018
The screen above indicates that the UPS is in frequency conversion mode and the bypass
output is restricted. For frequency conversion mode settings, please refer to
7.10.2 Mode
Setting
and
6.2.6 Frequency Conversion Mode Start-up Procedures
.
8
Bypass
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
2
WARNING
LOG IN
Administrator
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
Power Flow
Summary
System Status
10:15
May 25,2018
After the Delta or non-Delta external maintenance bypass cabinet’s manual bypass breaker
or switch (Q3) is turned on, the UPS will be switched to manual bypass mode, and the
screen above will appear. Before maintenance personnel perform maintenance, the UPS
must be switched to this mode and it must be ensured that all input power and battery power
are disconnected. After power disconnection, the LCD will be off. If there is any sudden
malfunction in the bypass, the loads will lose power and become unprotected. Please refer to
6.2.4 Manual Bypass Mode Start-up Procedures
.
Содержание Modulon DPH 200kVA
Страница 26: ...2 14 Modulon DPH Series...
Страница 62: ...3 36 Modulon DPH Series...
Страница 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 213: ...9 1 9 Maintenance Maintenance 9...
Страница 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Страница 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Страница 228: ...A1 4 Modulon DPH Series...
Страница 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 231: ......
Страница 232: ...5013255601...