2-13
2
ௐ ௐ
Introduction
Tri-color LED
Indicator
Status
Meaning
Yellow
ON
1. The UPS is running in bypass mode and the text
‘Bypass’
appears in the upper right corner of the
screen.
2. The UPS is running in battery mode and the text
‘Battery’
appears in the upper right corner of the screen.
3. The UPS is running in standby mode and the text
‘Standby’
appears in the upper right corner of the
screen.
4. The UPS is in the soft start status and the text
‘Softstart’
appears in the upper right corner of the screen.
5. The UPS is in the energy recycle status and the text
‘Energy Recycle’
appears in the upper right corner of
the screen.
6. There is a minor or medium warning and the buzzers
sound.
Warning Level
Buzzer Frequency
Minor
The buzzers beep 0.5 second for
every three seconds.
Medium
The buzzers beep 0.5 second for
every second.
To clear the warning, please refer to
10. Troubleshooting
.
Red
ON
There is a major warning and the buzzers sound.
Warning Level
Buzzer Frequency
Major
Long beep
To clear the warning, please refer to
10. Troubleshooting
.
Содержание Modulon DPH 200kVA
Страница 26: ...2 14 Modulon DPH Series...
Страница 62: ...3 36 Modulon DPH Series...
Страница 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 213: ...9 1 9 Maintenance Maintenance 9...
Страница 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Страница 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Страница 228: ...A1 4 Modulon DPH Series...
Страница 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 231: ......
Страница 232: ...5013255601...