Quick Installation Guide for Solar Power Inverter M50A_12s EU V4 EN 2018-10-24
Baud rate for RS485
E-Today: 0kWh
Power: 0W
Status: On Grid
12.Jun 2016 16:02
1.
If the default information is displayed, press the
EXIT
button to open the main menu
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
General Settings
entry and then press
the
ENT
button
Protocoll
Baud rate
Date & Time
Language
3.
Use the buttons
and
to select the entry
Baud Rate
and press the
ENT
button
38400
19200
9600
4.
Use the
and
buttons to configure a value and then press the
ENT
button
Repeat the procedure for the other settings
Active power limitation
Change this setting only after consultation with
Delta customer service
To change this setting, you need a special
password that you receive from Delta customer
service. You can find the contact information on
the back of this document
E-Today: 0kWh
Power: 0W
Status: On Grid
12.Jun 2016 16:02
1.
If the default information is displayed, press the
EXIT
button to open the main menu
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry and then press
the
ENT
button
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
Enter the password provided by Delta customer service
Use the
and
buttons to set the individual numerals
Press the
ENT
button to confirm a numeral.
AC Connection: 3P4W
EPO: Normal Open
Anti-islanding: ON
Max. Power: 55000W
Return to Factory
4.
Use the
and
buttons to select the
Max. Power
entry and then press the
ENT
button
5.
Use the
and
buttons to configure a value and then press the
ENT
button
Commissioning – further settings (optional)