SNMP IPv6 for UPS
Configuration
Go to
Monitor
Ȼ
Environment
Ȼ
Configuration
to configure the Warning
Threshold, Alarm Threshold, Title and Type. Please note that you can use the
two dip switches to set different operation modes. Please see the table below
for detail information.
http://192.168.1.100/
Dip 1 Dip 2
Opeation
Mode
Description
OFF
OFF
Normal Mode
The SNMP IPv6 works with the UPS. It provides the
UPS’s status information and parameters through
a network system.
OFF
ON
Pass Through
Mode
The SNMP IPv6 stops polling the UPS but transfers
the communication data between the console
port and the UPS.
ON
OFF
Sensor Mode
(with
EnviroProbe)
The SNMP IPv6 works with the UPS and an option-
al EnviroProbe. It provides the UPS’s information
and the environmental parameters (temperature,
humidity, etc).
ON
ON
Configuration
Mode
In this mode, the user can login through the con-
sole port and configure the SNMP IPv6’s settings.
Please refer to
4-4 Configuring through COM
Port.