InfraSuite EnviroStation
47
For
EnviroProbe 1200 (EMS1200)
The EnviroProbe 1200 (EMS1200) provides two analog inputs, one analog
output and one water-leakage detection. In this page, select
an
ID
first and
then set up
Title
and
Type
. Click
Enable
if you wish to enable the device.
Please note that the
ID
means the ID No. you set up for your EnviroProbe
1200 (EMS1200) using its ID DIP switches (please see
3.3 EnviroProbe
).
You can set up the following:
1) Analog
Input
Set up each analog input’s
((ADC-a)*b/c-d)
,
Title
and
Event Settings
.
Click the color bar in
Event Settings
to change event types for different
thresholds of analog inputs. Green, yellow, and red mean normal,
warning, and alarm events respectively.
2) Leakage
Set up leakage’s
Sensitivity
,
Title
and
Event Type
. If you check the
Buzzer Enable
box, the EnviroProbe 1200 (EMS1200) will enable
buzzer when it detects water leakage.
3) Analog
Output
Set up analog output (
Automatic
or
Manual)
,
Title
and
Control
. If
Manual
is selected,
Reaction
(please see
5.2.1 Management -
Reaction
) won’t be able to control analog output.