Delta InfraSuite EMS

User Manual

The power behind competitiveness

Environmental Management System

EnviroStation 

Содержание EnviroStation EMS2000

Страница 1: ...www deltapowersolutions com Delta InfraSuite EMS User Manual The power behind competitiveness Environmental Management System EnviroStation...

Страница 2: ...will continuously improve and develop the product changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes Delta will make...

Страница 3: ...3 1 RACK MOUNT INSTALLATION 10 3 2 RS485 11 3 3 ENVIROPROBE 12 3 4 DIGITAL INPUT 13 3 5 SENSOR HUB 14 3 6 ANALOG INPUT 16 3 7 RELAY OUTPUT 17 3 8 ALARM BEACON 17 3 9 PDU INSTALLATION 18 CHAPTER 4 SYS...

Страница 4: ...I 36 5 1 2 History 37 Event Log 37 Energy Log 38 Energy Compare 39 Data Log 39 Configuration 40 5 1 3 About 41 Information 41 5 2 DEVICE 42 5 2 1 Management 42 Sensor HUB 42 Digital Input 43 Analog In...

Страница 5: ...Web 57 Console 59 FTP 60 Time Server 60 Syslog 61 Batch Configuration 62 Upgrade 63 5 3 2 Notification 64 SNMP Access 64 SNMPv3 USM 65 SNMP Trap 65 Mail Server 66 CHAPTER 6 SNMP DEVICE FIRMWARE UPGRAD...

Страница 6: ...f flammable substances Do not attempt to disassemble the unit which contains potentially hazardous voltages Only trained technicians are allowed to perform this action Do not attempt to perform any in...

Страница 7: ...C 20100323 000158 CE EMI EN55022 CISPR 22 Class A EMS EN55024 IEC 61000 4 2 ESD Test IEC 61000 4 3 RS Test IEC 61000 4 4 EFT Test IEC 61000 4 6 CS Test IEC 61000 4 5 Surge Test Level 3 Air 8 KV Conta...

Страница 8: ...0 has one temperature humidity sensor and four digital inputs The EnviroProbe 1100 EMS1100 has four digital outputs and the EnviroProbe 1200 EMS1200 has two analog inputs one analog output and one wat...

Страница 9: ...s each PDU s load frequency watt accumulated power consumption etc IPMI supported Supports IPMI version 1 5 version 2 0 Flexible reaction setup You can create your own reaction rules Based on the inpu...

Страница 10: ...ocesses signals 2 3 Package Contents Please carefully verify EnviroStation and the included accessories Contact your dealer if any item is missing or damaged Should you return the items for any reason...

Страница 11: ...SET Door contact sensor 1 SET AC power cord 1 PC RJ45 to DB9 cable 1 PC Standard CAT5 cable 1 PC Extension cable for leakage sensor 1 PC You will need the following items Peripheral devices such as t...

Страница 12: ...ce On green Connected Off Not connected Fault LED Indicates whether an internal fault has occurred On red Fault occurred Off Normal Relay Output LEDs On green The Relay Output is switched to NC Normal...

Страница 13: ...eous flashing every 500ms Initialization failure Warning Do NOT disconnect the EnviroStation s input power during initialization or firmware upgrade This could result in data loss or damage to the Env...

Страница 14: ...dard CAT5 cables with straight through wiring Digital Input Four input contact devices can be connected to EnviroStation The wet contact active rating is 5 24Vdc 1 9mA Analog Input Connects four analo...

Страница 15: ...t Installation Step 1 Choose a location in the rack On the vertical mounting rails insert the provided cage nuts Step 2 Using two screws attach two bracket ears provided in the accessory box to each e...

Страница 16: ...at the power source is rated between 100 240V and is well grounded 3 2 RS485 EnviroStation provides two RS485 ports for devices that communicate through the Modbus protocol such as power meters and do...

Страница 17: ...viroProbe is connected please also make sure that it is set to Rt Yes Step 3 Set the ID DIP switch to assign an ID for each EnviroProbe please refer to the EnviroProbe User Manual No particular numeri...

Страница 18: ...and always make sure that you are connecting the correct ports before you plug in 3 4 Digital Input The EnviroStation provides four Digital Inputs Wet and Dry Contacts can be connected for application...

Страница 19: ...4Vdc 1 9mA 3 5 Sensor HUB In the accessory box you can find eight provided Sensor HUB adapters RJ45 to 6 pin terminal connector which are used to connect peripheral devices for purposes such as smoke...

Страница 20: ...requirement of the devices you are connecting different terminal connections are required Please see the following figures 1 12Vdc is provided by connecting the following two terminal points 12V and...

Страница 21: ...and 2 can be connected to a voltage 0 10Vdc or current 0 20mA source Please see the following illustrations The Analog Input 3 is dedicated to a 2 wire or 3 wire RTD Resistance Temperature Detector in...

Страница 22: ...y specific events to alert you to any unusual situations To install the Alarm Beacon a provided terminal block and a Sensor HUB adapter are needed Step 1 Plug the terminal block into the green termina...

Страница 23: ...with up to 16 PDU devices different models are allowed If you wish to cascade PDU devices please set a unique ID No 0 15 for each PDU with its own four DIP switches see Table 3 1 Table 3 1 Settings of...

Страница 24: ...to the PDU s RS232 2 port If you need to cascade several PDU devices please use the RS232 cables provided in your PDU devices Please refer to the figure below Step 3 After installation please visit I...

Страница 25: ...ion to set up your EnviroStation Please see 4 4 Configuring through COM Port NOTE 1 To ensure system security it is highly recommended that you change your account and password after the first login 2...

Страница 26: ...r the account types are listed as follows 1 Administrator Allowed to modify all settings 2 Device Manager Allowed to modify device related settings 3 Read Only User Only allowed to view settings witho...

Страница 27: ...t from EnviroStation s rear panel to the network Step 2 Make sure the workstation and the EnviroStation are on the same LAN Step 3 Insert the provided CD in the CD ROM drive From the root directory la...

Страница 28: ...nt to modify from the Device List Click Modify and enter account and password default admin password case sensitive Step 6 Click Configuration to configure network settings NOTE Refer to Chapter 5 Ins...

Страница 29: ...nsitive The Main Menu will appear on the screen Please refer to 4 5 Configuring via Text Mode for more information NOTE 1 The EnviroStation will terminate idle connections after 60 seconds 2 Refer to...

Страница 30: ...not include the program a free alternative Telnet SSH client PuTTy can be downloaded from http www putty org Step 3 Enter a name choose an icon for the connection and click OK From the dropdown menu c...

Страница 31: ...blished log in with account password Default admin password case sensitive Once you are logged in the Main Menu appears on the screen Please refer to 4 5 Configuring via Text Mode for more information...

Страница 32: ...llowed Disable 2 Server The RADIUS server name 3 Secret The RADIUS secret 4 Port The RADIUS port number 1812 5 Administrator Account admin 6 Administrator Password The default account password for the...

Страница 33: ...only permitted to change device related settings password a Device Limitation Restrict login area of the Device Manager Only in This LAN b Read Only User Account user c Read Only User Password The def...

Страница 34: ...work default gateway 9 IPv6 DNS IP IPv6 Domain Name Server IP address a DHCPv6 Enable disable DHCPv6 protocol Enable b Host Name NetBIOS The Host Name for the EnviroStation INSIGHTPOWER c System Conta...

Страница 35: ...Server Enable disable HTTPS protocol Enable 3 Telnet Server Enable disable Telnet protocol Enable 4 SSH SFTP Server Enable disable SSH SFTP protocol Enable 5 FTP Server Enable disable FTP protocol Dis...

Страница 36: ...t Name e Syslog Server 3 The remote syslog Host Name f Syslog Server 4 The remote syslog Host Name g SNMP Get Set Port The SNMP networking port 161 Time Server You can manually adjust time and date fo...

Страница 37: ...d time server for SNTP 5 Manual Date Set the date manually If the Time Selection is set to Manual 01 01 2000 6 Manual Time Set the date manually If the Time Selection is set to Manual 00 00 00 Soft Re...

Страница 38: ...ted connection enter https InsightPower or https 192 168 1 100 Step 3 When connection is established the EnviroStation Login page appears Enter your account and password Default admin password NOTE 1...

Страница 39: ...the information of System Status Sensor HUB Digital Input Analog Input Relay Output Delta Bus RS485 PDU and IPMI status Status This page presents a status overview of connected devices The values will...

Страница 40: ...ed EnviroProbes To add or remove Delta Bus devices click Configuration on the bottom right corner or go to Management Delta Bus RS485 To check RS485 device parameters go to Information RS485 To add or...

Страница 41: ...vant readings For more information about the data log and energy log please refer to 5 1 2 History Event Log and 5 1 2 History Energy Log If you want to enable a PDU unit please click Configuration at...

Страница 42: ...number of entries 1 000 is reached You can also download the entire event log archive event_log xls recorded during an assigned period of time on your computer Date The date when the event occurred T...

Страница 43: ...y Energy Log to look up selected PDUs energy logs You can set up a specific time click the Display Detail Data button to view detailed records and click the Download button to download the energy logs...

Страница 44: ...erwritten when the maximum number of entries 8 000 is reached Data Log Go to Monitor History Data Log to see the analog inputs data logs EnviroProbe sensors data logs and a specific PDU s data log rec...

Страница 45: ...u can also assign Save Data Interval and Save Energy Interval Clear History Data Empty the data log only Clear Event Log Empty the event log only Clear Energy Data Empty the energy log and energy comp...

Страница 46: ...aSuite EnviroStation 41 5 1 3 About Information Go to Monitor About Information to see the version of your InsightPower SNMP IPv6 for EnviroStation and other information about OpenSSL toolkit and lice...

Страница 47: ...ocol PDU IPMI Device IPMI Template and Reaction Sensor HUB NO NC Stands for Normal Open and Normal Close If Normal Open is selected an event is triggered when 1 Dry Contact is closed or 2 Wet Contact...

Страница 48: ...he power Power is cut off during the period of time specified in the Active Period box Power resumes after the given duration If the specified Active Period is 0 power does not resume Digital Input NO...

Страница 49: ...according to the following formula ADC a b c d You can select the unit scale and define the unit string for the translated values Title You can entitle devices for identification Warning Alarm You can...

Страница 50: ...itle You can entitle devices for identification Delta Bus The EnviroStation communicates with EnviroProbes through the Delta Bus There are three types of EnviroProbes 1 EnviroProbe EMS1000 2 EnviroPro...

Страница 51: ...h digital output s Operation Period and Title Select Automatic to enable automatic linking between a specific digital output and Reaction please see 5 2 1 Management Reaction Select Manual to set the...

Страница 52: ...p the following 1 Analog Input Set up each analog input s ADC a b c d Title and Event Settings Click the color bar in Event Settings to change event types for different thresholds of analog inputs Gre...

Страница 53: ...th a different baud rate data bits parity and stop bit EnviroStation communicates with up to 16 Modbus devices in an RS485 port You can individually select protocol for each Modbus device from the dro...

Страница 54: ...aSuite EnviroStation 49 Protocol In this page you can add modify or delete protocols You can also export or import protocols from files for backup purposes Each protocol contains 32 values and 32 stat...

Страница 55: ...le box the text mode will be disabled After you select PDU ID No and click Submit the EnviroStation will monitor the PDU units accordingly IPMI Device IPMI Scan Setting You can set up IPMI Scan Interv...

Страница 56: ...tation 51 Device scan result will appear after the scan process is done You can add a device that you would like to monitor if you check the Add box give a device name specify its template and then cl...

Страница 57: ...ny sensors that you want to monitor Template Scan To scan an IPMI template you have to enter the Username Password server s IP Address IPMI version and Cipher Suite After clicking the Scan button the...

Страница 58: ...hat you like and group them into a new template by giving a new template name in the Template Name column After clicking the Add button the new template name will be added into the template list You c...

Страница 59: ...setting up the Period the EnviroStation will regularly execute the Reaction Rule If the Reaction Rule s all conditions are met there will be corresponding outputs If the Period is 0 and the Reaction R...

Страница 60: ...se RADIUS box key in required information including Server Secret and Port default 1812 and click submit to enable RADIUS You can define service types for Administrator De vice Manager and Read Only U...

Страница 61: ...automatically assigns an IP address to the EnviroStation 2 IP Address The IP address in dotted format e g 192 168 1 100 3 Subnet Mask The Subnet Mask for your network e g 255 255 255 0 4 Gateway IP T...

Страница 62: ...DNS V6IP The IP address for the IPv6 domain name server System 1 Host Name The SNMP Host Name on the network 2 System Contactor System contact information 3 System Location System location information...

Страница 63: ...nsure connection security between the EnviroStation and the connecting workstation SSL certificates can be used to encrypt and secure the integrity of transmitting data 2 Certificate File This allows...

Страница 64: ...le disable Telnet connection SSH SFTP Enable disable SSH SFTP connection Telnet Port Assign a Telnet port number default 23 SSH Port Assign an SSH protocol port number default 22 Host Key DSA RSA Key...

Страница 65: ...tocol FTP Enable disable FTP connection FTP Port Assign an FTP port number default 21 Time Server You can manually set the time and date or enable automatic time synchronization with SNTP servers Plea...

Страница 66: ...the first responding server 3 Enable Daylight Saving Check to enable daylight saving time During this period the EnviroStation adjusts time forward one hour Manual If a time server is not accessible...

Страница 67: ...includes settings saved in the Management and Administration tabs To download a configuration file simply click Download To upload a configuration file click Choose File select the file you wish to up...

Страница 68: ...If you need to modify the command lines please do not delete the unmodified ones They should be left intact to assure the integrity of the configuration file Upgrade Check for latest firmware upgrades...

Страница 69: ...ions that call for administrative attention To prevent unauthorized access you can specify the NMS IP addresses that are allowed to access with their respective Community Strings and access levels The...

Страница 70: ...ne their respective Security Levels Auth Passwords Priv Passwords and Access Level SNMP Trap SNMP Trap alerts users to event occurrences in your monitored environment To enable SNMP Trap you must add...

Страница 71: ...e target address Alarm Only Alarm event notifications are sent to the target address Mail Server You can set up an SMTP Server and specify a list of E mail recipients who will receive notifications wh...

Страница 72: ...ail server login password Receiver The recipients E mail addresses Event Level Select the Event Level that when triggered an E mail notification is sent to the corresponding recipient 1 Information Al...

Страница 73: ...grade for SNMP devices via LAN Please refer to the following instructions Step 1 The subnet mask allows you to refine the device discovery range in the specified subnets Make sure the SNMP device you...

Страница 74: ...List click Modify and key in Administrator account and password Step 4 Click Upgrade The upgrade dialog box pops up Click Browse to select a valid firmware binary file Verify the firmware version lis...

Страница 75: ...6 SNMP Device Firmware Upgrade 70 Step 5 The upgrade process should take about 20 seconds Step 6 When the upgrade is completed the following dialog box appears It takes about 1 minute for the device t...

Страница 76: ...on and EnviroStation To check connection between the EnviroStation and workstation in Windows please launch DOS prompt mode Start Run key in cmd and press enter In Linux launch Shell Enter the followi...

Страница 77: ...you can still manually force it to refresh by entering the following command nbtstat R in DOS prompt mode or shell After that you can now connect to the EnviroStation by its Host Name Please also ens...

Страница 78: ...sts use a network cable to cross link your EnviroStation and the workstation Ping the EnviroStation s default or static IP address according to your configurations If a ping response is successfully r...

Страница 79: ...IP address for the EnviroStation To learn more information regarding IPv6 compatibility please visit IETF http tools ietf org html or IPv6 Ready Logo Program http www ipv6ready org Q12 How to generat...

Страница 80: ...r SNMP IPv6 for EnviroStation Web Please refer to 5 3 Administration Console for more information For Windows 1 Please download and install PuTTY from http www putty org 2 Run puttygen exe from the in...

Страница 81: ...Pv6 automatically imports your settings after the files are uploaded to the designated directories Refer to the following table Directory Files config_snmp snmp ini config_system configure ini ssh_dsa...

Страница 82: ...hich is assigned from SNMPv3 USM table n The Context Name which is assigned from SNMPv3 USM table t Timeout in seconds ip The IP address of the EnviroStation oid The next available SNMP OID For exampl...

Страница 83: ...cy 1 C with 3 wire PT100 Detect Voltage 1V Leakage alarm signal with S 1FP leak sensor Network Connection RJ45 jack connector Output 12V 0 8A max 24V 1 0A max Sensor HUB One port limit 0 6A Delta Bus...

Страница 84: ...esistible force i e war fire natural disaster etc and this warranty also expressly excludes all incidental and consequential damages Maintenance service for a fee is provided for any damage out of the...