http://www.delta.com.tw/industrialautomation/
2006-10-24
5011650900-H2E0
High-Speed, Multi-Functional
Programmable Logic Controller
Instruction Sheet
Warning
3
This instruction sheet only provides introductory information on electrical specification, functions, wiring,
trouble-shooting and peripherals. For detailed information on programming and instructions, please refer to
“DVP-PLC Application Manual: Programming”. For how to purchase its peripheral devices, please refers to the
manual enclosed with the product.
3
DVP-EH2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key
or specific tools are required for opening the enclosure) in case danger and damage on the device may occur.
3
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power and Do NOT tough any terminal when the power is switched on.
Make sure the groud terminal
is correctly grounded in order to prevent electromagnetic interference.
X
Introduction
1.1 Model Explanation & Peripherals
Nameplate Explanation
100~240VAC 50/60Hz 30VA MAX
MODEL
POWER INPUT
OUTPUTMODULE 2.0A 250Vac 50/60Hz RES LOAD
32EH00R2T6160018
VX.XX
DELTA ELECTRONICS,INC.
MADE IN XXXXXX
DVP32EH00R2
Delta PLC model name
Power input specification
Output module specification
Barcode & series No.
Firmware version
Model/Serial No. Explanation
32EH00R2 0 T 6 16 0018
Model name
Version No.
Production plant (Taoyuan)
Production year (2006)
Production week
Production No.
1.2 Product Profile & Outline
1
2
3
5
9
4
9
6
10
5
4
7
8
Open COM1 cover
c
Communication port cover
h
Extension module connection port cover
d
I/O terminal cover
i
Input indicator
e
Function card/memory card cover
j
Output indicator
f
I/O terminals
k
DIN rail clip
g
I/O terminal No.
l
DIN rail (35mm)
3
1
2
6
7
1
2
5
4
8
Open COM2 cover
c
Mounting screw
g
Memory card port
d
Direct mounting hole
h
POWER/RUN/BAT.LOW/ERROR indicator
e
Battery socket
i
Extension module connection port
f
Function card mounting hole
Removable Terminal Block
COM 2 (RS-485)
RUN / STOP SWITCH
VR 0
VR 1
COM 1 (RS-232)
Battery
Remove RS-485
terminal
Part
Description
COM2 (RS-485)
For both master & slave modes
RUN/STOP switch
PLC RUN/STOP control
VR0
Enable M1178/corresponding
value of D1178
VR1
Enable M1179/corresponding
value of D1179
COM1 (RS-232)
For slave mode
Battery
Shall be changed within 1 min.
1.3 Installation of function card/memory card (optional accessories)
Remove function card
Remove memory card
Close the cover
For details, see the instruction sheets of these accessories.
Y
Electrical
Specifications
Model
Item
16EH00
2
20EH00
2
32EH00
2
40EH00
2
48EH00
2
64EH00
2
80EH00
2
Power supply
voltage
100 ~240VAC (-15% ~ 10%); 50/60Hz
±
5%
Fuse capacity
2A/250VAC
Power
consumption
50VA 50VA 60VA 60VA 60VA 80VA 80VA
DC24V current
supply
500mA 500mA 500mA 500mA 500mA 500mA 500mA
Power protection
DC24V; output short-circuited
Withstand voltage
1500VAC (Primary-Secondary); 1500VAC (Primary-PE); 500VAC (Secondary-PE)
Insulation
resistance
>
5 M
Ω
(all I/O point-to-ground: 500VDC)
Noise immunity
ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m
Earth
The diameter of grounding wire shall not be less than that of L, N terminal of the power. (When many PLCs are
in use at the same time, please make sure every PLC is properly grounded.)
Operation/storage
Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40 ºC ~ 70 ºC (temperature); 5 ~ 95% (humidity)
Vibration/shock
immunity
International standards: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST Ea)
Weight
(g)
500/480 520/500 652/612 710/675 748/688 836/756 948/848
Input point specifications
24VDC single common port input
Spec.
Items
Low speed
High speed (200KHz)
Note
Input wiring type
Change wiring from S/S to SINK or SOURCE
Input indicator
LED display; light on = ON, light off = OFF
Input voltage
24VDC
±
10%
Off
On 16VDC
±
10%
Active Level
On
Off 12VDC
±
10%
Response Time / Noise Immunity
10 ms
0.5us
Input point X0 ~ X7, X10 ~ X17
can conduct 10 ~ 60ms digital
filter adjustment
Output point specifications
Single common port transistor output
Spec.
Items
Low speed
High speed*
Single common port relay output
Max. frequency
10KHz
200KHz
Load ON/OFF control
Output indicator
LED display; light on = ON, light off = OFF
Min. load
-
2mA/DC power supply
Working voltage
5 ~ 30VDC
<
250VAC, 30VDC
Insulation
Photocoupler isolation
Magnetic isolation
Current specification
0.3A/1 point @ 40ºC
<1KHz, 0.3A/1 point @ 40°C
≧
1KHz, 30mA/1 point @ 40°C
2A/1 point (5A/COM)
75 VA (conductive), 90W (resistive)
Off
On 20us
Max. output
delay time
On
Off 30us
0.2us 10ms
Over-current protection
N/A
Mechanical life
N/A
2×10
7
times (without load)
Electrical life
N/A
1.5×10
5
times (5A 30VDC); 5×10
5
times (3A 120VAC); 3×10
4
times
(5A 250VAC)
*High-speed output points (Y0, Y2) are only in DVP20EH2 and DVP32EH2; high-speed output points (Y0, Y1, Y2, Y3, Y4, Y6) are only in
DVP40EH2.
Z
Installation & Wiring
3.1 Dimension
4.6 X
2
W
W1
80
.0
9
0.
0
82.2
Model
W (mm)
W1 (mm)
DVP16EH00R2/T2 113
103
DVP20EH00R2/T2 113
103
DVP32EH00R2/T2 143.5 133.5
DVP40EH00R2/T2 158.8 153.8
DVP48EH00R2/T2 174
164
DVP64EH00R2/T2 212
202
DVP80EH00R2/T2 276
266
3.2 Wiring
terminals
16EH2
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1 Y2 Y3
Y4
Y5 Y6
C6
C2
C1
C0
S/S
Y7
C3 C4 C5
C7
20EH2
X13
X12
X11
X10
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1
C1
Y2
Y3
Y4
C3
C0
S/S
C2
C4
+24V
24G
Y6
Y5
Y7
32EH2
Relay
X17
X16
X15
X14
X13
X12
X11
X10
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1
Y2
Y3
Y4 Y5
Y6
C3
C2
C1
C0
Y7
Y12
Y13
Y16
Y17
Y15
Y14
Y11
Y10
S/S
32EH2
Transistor
X17
X16
X15
X14
X13
X12
X11
X10
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1
C1
Y2
Y3 Y4
Y6
C5
C3
C0
Y5
Y12
Y11
Y17
Y16
Y14
Y13
Y10
Y7
S/S
C2
C6 Y15
C4
40EH2
Relay
X23
X22
X21
X20
X17
X16
X15
X14
X13
X12
X11
X10
X7
X6
X5
X4
24G Y0
C0
Y2 Y3
C3
C5
C4
C2
24V
Y12
Y10
Y6
Y4
S/S
Y14 Y16
Y15
C1
Y5
Y11
C6
X24 X26
X25 X27
Y1
Y7
Y13
Y17
X1
40EH2
Transistor
X23
X22
X21
X20
X17
X16
X15
X14
X13
X12
X11
X10
X7
X6
X5
X4
24G Y0
C0
Y2 Y3
C4
C2
C1
24V
Y12
Y10
Y6
Y4
S/S
Y14 Y16
Y15
Y5
Y11
C5
X24 X26
X25 X27
Y1
Y7
Y13
Y17
X1
C3
48EH2
X17
X16
X15
X14
X13
X12
X11
X10
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1
Y2
Y3
Y4 Y5
Y6
C3
C2
C1
C0
Y7
Y12
Y13
Y16
Y17
Y15
Y14
Y11
Y10
S/S
X27
X26
X25
X24
X23
X22
X21
X20
C4 Y21
Y22
Y27
Y23
Y26
Y24
Y20
Y25
64EH2
X17
X16
X15
X14
X13
X12
X11
X10
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1
Y2
Y3
Y4 Y5
Y6
C3
C2
C1
C0
Y7
Y12
Y13
Y16
Y17
Y15
Y14
Y11
Y10
S/S
X27
X26
X25
X24
X23
X22
X21
X20
C4 Y22
Y21
Y27
Y24
Y25
Y23
Y20
Y26
X37
X36
X35
X34
X33
X32
X31
X30
C5 Y31
Y32
Y37
Y33
Y36
Y34
Y30
Y35
80EH2
X15
X14
X13
X12
X11
X10
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1
Y2
Y3
Y4 Y5
Y6
C3
C2
C1
C0
Y7
Y12
Y13
Y16
Y17
Y15
Y14
Y11
Y10
S/S
X23
X22
X21
X20
X17
X16
C4 Y22
Y21
Y27
Y25
Y23
Y20
Y26
X31
X30
X33
X32
X27
X26
X25
X24
C6 Y32
Y31
Y37
Y34
Y35
Y33
Y30
Y36
X35
X34
X37
X36
X41
X40
X43
X42
X45
X44
X47
X46
C5
Y24
C7 Y42
Y41
Y47
Y44
Y45
Y43
Y40
Y46
3.3 Installation
How to install DIN rail
DVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and 7.5mm
in depth. When mounting PLC to DIN rail, be sure to use the end bracket to stop any
side-to-side movement of PLC and reduce the chance of wires being loosen. A small
retaining clip is at the bottom of PLC. To secure PLC to DIN rail, place the clip onto the rail
and gently push it up. To remove it, pull the retaining clip down and gently remove PLC
from DIN rail, as shown in the figure.
How to screw
Please use M4 screw according to the dimension of the product.
Please install PLC in an enclosure with sufficient space around it to allow heat
dissipation as shown in the figure.
DVP MPU
> 50mm
> 50mm