3.4 Wiring 

Please note that: 
1.  Use O-type or Y-type terminal. See the figure in the right for its 

specification. PLC terminal screws should be tightened to 5 ~ 8 
kg-cm (4.3 ~ 6.9 in-Ibs) and please use only 60/75 ºC copper 
conductor. 

2.  DO NOT wire empty terminal 

 • 

 

3.  DO NOT drop tiny metallic conductor into the PLC while screwing 

and wiring. Tear off the sticker on the heat dissipation hole for 
preventing alien substances from dropping in, to ensure normal 
heat dissipation of the PLC. 

To suit M3.5 screw terminals

Below 6.2

Below 6.2

 

 

3.5 Power 

input 

wiring 

The power input of DVP-EH2 series is AC. When operating the PLC, please make sure that: 
1.  The input voltage should be current and its range should be 100VAC ~ 240VAC. The power should be 

connected to L and N terminals. Wiring AC110V or AC220V to +24V terminal or input terminal will result in 
serious damage on the PLC. 

2.  The AC power input for PLC MPU and I/O extension modules should be ON or OFF at the same time. 
3.  Use wires of 1.6mm (or longer) for the grounding of PLC MPU. 
4.  The power shutdown of less than 10 ms will not affect the operation of the PLC. However, power shutdown time 

that is too long or the drop of power voltage will stop the operation of the PLC and all outputs will go OFF. When 
the power supply turns normal again, the PLC will automatically return to its operation. Please be aware of the 
latched auxiliary relays and registers inside the PLC when programming. 

 

AC Power Input 

L

 

N

 

2.0 A

DC/DC

 

+5V

 

+24V

 

24G

 

S/S

 

X0

 

X1

 

X2

 

100~240VAC

 

 

0.5A is the maximum power supply for +24V power supply output terminal. DO NOT connect other external 
power supplies to this terminal. Every input terminal requires 6 ~ 7mA to be driven; e.g. the 16-point input will 
require approximately 100mA. Therefore, +24V cannot give output to extermal load that is more than 400mA. 

 

3.6 Safety 

wiring 

Since a PLC controls many devices, actions of any device may affect actions of other devices and the breakdown 
of any one device may cause the breakdown of the whole auto-control system and danger. Therefore, we suggest 
you wire a protection circuit at the power input terminal, as shown in the figure below. 
 

c

 

AC power supply load 

d

 

Power circuit protection fuse (3A

 

e

 

Power indicator 

f

 

Emergency stop 

This button can cut off the system power supply when accidental 
emergency takes place.   

g

 

System circuit isolation device 

The device is made of electromagnetic contactor and relay as the 
switch to prevent the instability of system when the power is 
intermittently supplied.   

h

 

DVP-PLC (main processing unit) 

i

 

Earth 

MC

MC

N

L

1

1

2

3

4

5

6

7

8

Guard

Limit

MC

 

j

 

Power supply 

AC: 100 ~ 240VAC, 50/60Hz 

 

3.7 Input 

point 

wiring 

There are two types of DC inputs, SINK and SOURCE. 

Input point loop equivalent circuit 

Wiring loop 

DC Signal IN 

 

S/S

X0

Sinking

 

SINK

 mode 

(common port for current input 
S/S) 

24VDC

24G

X0

S/S

+24V

SINK

+5V

 

24G

S/S X0 X1 X2

+24V

Sink Type

 

 

Input point loop equivalent circuit 

Wiring loop 

DC Signal IN 

S/S

X0

Sourcing

 

SOURCE

 mode 

(common port for current 
output S/S) 

24VDC

24G

X0

S/S

+24V

SOURCE

+5V

 

24G

S/S X0 X1 X2

+24V

Source Type

 

 

3.8 Output 

point 

wiring 

™

 Relay (R) contact circuit wiring 

Y0

RY

LED

C0

LOAD

POWER

DVP-**-**-**-R

RELAY OUTPUT

 

2

3

1

5

C0 Y0 Y1

C1 Y3 Y4 C2 Y6 Y7

4

MC1

MC2

7

10

3

2

8

9

6

 

c

 

Flywheel diode: To extend the life span of contact 

d

 

Emergency stop: Uses external switch 

e

 

Fuse: Uses 5 ~ 10A fuse at the common port of output contacts to protect the output circuit.   

f

 

Varistor: To reduce the interference on AC load 

g

 

Empty terminal: not in use 

h

 

DC power supply 

i

 

Neon indicator 

j

 

AC power supply 

k

 

Incandescent light (resistive load) 

l

 

Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC internal program, to ensure 
safety protection in case of any unexpected errors.   

 

™

 Transistor (T) contact circuit wiring

 

Y0

LED

C0

TRANSISTOR OUTPUT

LOAD

DVP-**-**-**-T

< 0.5A

 

MC1

MC2

2

3

1

C0 Y0

Y1 C1 Y4 Y5 Y6 Y7

5

4

5

3

4

 

c

 

DC power supply 

d

 

Emergency stop 

e

 

Circuit protection fuse 

f

 

Flywheel diode + inductive load 

g

 

Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC internal program, to ensure 
safety protection in case of any unexpected errors. 

[

 

Trial Operation

 

™

 Power indication 

 
The “POWER” LED indicator on the front panel of PLC MPU (or extension module) will be on (in green) when the 
MPU is powered. That the MPU is powered but the indicator is not on indicates that the 24VDC power supply of the 
PLC is overloaded. You have to remove the wiring at te24V and 24G and have another DC24V power 
supply ready. That the “ERROR” LED indicator flashes continuously indicates that the +24V power supply for the 
PLC is insufficient. 
 

™

 Low voltage indication

 

 
That the “LOW.V” indicator on the front panel of the PLC extension module is on indicates that the input voltage is 
insufficient. All outputs of the module are disabled at this time. 
 

™

 Preparation 

 
1.  Before powering DVP-EH2, be sure that you have checked if the I/O wiring is correct. You may damage the 

PLC if AC110V or AC220V is directly supplied to input terminals or the output wiring is short-circuited. 

 
2.  When the peripheral devices are used to write program into PLC: If the ERROR indicator does not flash, the 

program you are using is legal and PLC is waiting for RUN instruction from you. 

 
3.  You can use HPP to test “force On/Off” of output contacts. 
 

™

 Operation & test 

 

1.  If the ERROR indicator does not flash, you can use RUN/STOP switch or peripheral device (HPP or WPLSoft) 

to give RUN instruction and the RUN indicator should be continuously on at this time. That the RUN indicator 
does not flash indicates PLC has no program in it. 

 
2.  When PLC is in operation, use HPP or WPLSoft to monitor the set value or temporarily saved value in the 

timer, counter, and register and force On/Off of output contacts. That the ERROR indicator is on (not flashes) 
indicates that part of the program exceeds the preset time-out. In this case, you have to check the program 
and set On/Off of the power again (PLC automatically returns to STOP status at this time). 

 

™

 I/O response time 

 

How to calculate the response time from the input signal to output operation of the PLC: 
 

Response time = input delay time + program scan time (executed by the user) + output delay time 

 

Input delay time 

10ms (default); 0 ~ 60ms (adjustable). See the reference on how to use special register 
D1020 ~ D1021. 

Program scan time 

See the reference on how to use special register D1010. 

Output delay time 

Approx. 10ms for relay modules, 20 ~ 30us for transistor modules 

 
 

\

 

How to identify abnormality of PLC

 

To identify abnormality from the indicators on the panel, please check: 

™

 POWER indicator 

 

When PLC is powered, the POWER indicator on the front panel will be on (in green). If this indicator is not on when 
the PLC is powered, remove the wiring of +24V terminal. If this indicator turns on at this time, the +24V DC output 
is overloaded. In this case, DO NOT use DC power supply at +24V terminal and have another DC24V power 
supply ready. If this indicator turns off after the overload is eliminated, your PLC is malfunctioned. Send your PLC 
back to your distributor for repair. 
 

™

 RUN indicator 

 

Check your PLC status. When PLC is running, this indicator will be on. You can use HPP, the ladder diagram 
editing program or the switch on the panel to RUN or STOP PLC. 
 

™

 ERROR indicator 

 

1.  If you enter illegal program into PLC or use instructions or devices that exceed their range, this indicator will 

flash (approx. every 1 sec.). When this happens, you have to obtain the error code from D1004 and save the 
address where the error occurs in register D1137 (if the error is a general circuit error, the address of D1137 will 
be invalid). Find out the cause of the error, amend the program and resend the program to PLC. If you cannot 
connect to PLC and this indicator keeps flashing quickly (approx. every 0.2 sec.), there should be insufficient 
24VDC power supply. Please check if the 24VCD is overloaded. 

 

L

 

For details of error codes (in D1004, hex coding), see “DVP-PLC Application Manual: Programming” 

 

2.  If the ERROR indicator keeps flashing, you have to check the special relay M1008. M1008 is on indicates that 

the execution time of program loop exceeds the preset time-out (in D1000). In this case, turn the RUN/STOP 
switch to STOP, check the special register D1008 and obtain the location in the program where the time-out 
takes place. We suggest you use WDT instruction to correct this problem. 

 

™

 BAT.LOW indicator 

 

BAT.LOW indicator will be on when the battery is in low voltage. When this happens, change the battery as soon as 
possible in case your program and data saved in the latched area will be lost. 
 

L

 

The changing of battery has to be completed within 1 minute when the PLC is not powered in order to save your 

procedures and data in the PLC. 

 
After the power is switched off, the data in the latched area are stored in SRAM memory and its power is supplied 
by the battery. Therefore, when the battery is in low voltage and the power-off has been lasted for more than 1 
minute, the data in the latched area will be lost. If you need to permanently save the data in the latched area in the 
program and device D, refer to “Flash ROM permanently saved and recover mechanism” as stated below.   
 

Permanently saved mechanism 

You can use WPLSoft (Options -> PLC<=>Flash) to indicate whether to permanently store the data in the 
latched area in Flash ROM memory (new indicated data will replace all data previously saved in the memory). 

Recover mechanism 

If the battery is in low voltage (before the power is switched off when the BAT.LOW indicator is on) and the 
power is off for more than 1 minute, PLC will automatically restore the data in the latched area in the program 
and device D of Flash ROM into SRAM memory next time when it is re-powered. 

 
Battery life: 

Temperature (ºC) 

25 

50 

70 

Life (year) 

 

™

 Input indicator 

 

On/Off of input point is indicated by input indicator or monitored by HPP. When the action criteria of the input point 
are true, this indicator will be on. If abnormality is identified, check if the indicator and input circuit are normal. 
 

 

™

 Output indicator 

 

On/Off of output point is indicated by output indicator. When the output indicator (On/Off) does not correspond to 
the action of its load, please be aware of the follows: 
 
1.  The output contact may be melted or blocked out of overloading or short-circuited load, which will result in poor 

contact. 

 
2.  If you are suspicious that the output point may execute undesired action, check the output wiring circuit and 

whether the screw is properly tightened. 

 

™

 Accuracy (month/second) of RTC 

 

Temperature (ºC/ºF) 

0/32 

25/77 

55/131 

Max. inaccuracy (second) 

-117 

52 

-132 

 

 

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or 