background image

TECHNICAL DATASHEET

 

Sync DIN Rail Power Supply 

24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (July 2019, Rev. 04) 

 

3

 

Mechanical 

 

Case Cover / Chassis 

 

Plastic  

Dimensions (L x W x D) 

 

75 x 21 x 89.5 mm (2.95 x 0.83 x 3.52 inch) 

Unit Weight 

 

0.11 kg (0.24 lb) 

LED Indicator 

Green LED  DC OK 

Cooling System 

 

Convection 

Terminal 

Input  3 Pins (Rated 300V/16A) 

 

Output  2 Pins (Rated 300V/16A) 

Wire 

Input / Output  AWG 22-12 / AWG 20-12 

Mounting Rail 

 

Standard TS35 DIN Rail in accordance with EN 60715 

Noise (1 Meter from power supply) 

 

Sound Pressure Level (SPL) < 25dBA 

 

 

Environment 

 

Surrounding Air Temperature 

Operating  -20°C to +70°C (Cold start at -40°C @ 40% load) 

 

Storage  -40°C to +85°C 

Power De-rating 

Temperature  -10°C to -20°C de-rate power by 2% / °C 

> 55°C de-rate power by 3.33% / °C 

Operating Humidity 

  5 to 95% RH (Non-Condensing) 

Operating Altitude 

  0 to 2,000 Meters (6,560 ft.) 

Shock Test 

Non-Operating  IEC60068-2-27, Half Sine Wave: 50G for a duration of 11ms; 

3 times per direction, 9 times in total 

 

Operating  IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11ms; 

1 time in X axis 

Vibration 

Non-Operating  IEC 60068-2-6, Random: 5-500Hz; 2.09G

rms

, 20 min per axis 

for all X, Y, Z directions 

 

Operating  IEC 60068-2-6, Sine Wave: 10-500Hz; 2G peak; displacement 

of 0.35mm; 1 octave per min; 60 min per axis for all X, Y, Z 

directions 

Over Voltage Category 

  II 

Pollution Degree 

  2 

 

 

Protections 

 

Overvoltage 

< 34.8V, SELV Output, Latch Mode 

Overload / Overcurrent 

105~140% of rated load current, 

Foldback Mode (continuous current, voltage drops), 

Auto-recovery when the fault is removed 

Over Temperature 

< 75°C Surrounding Air Temperature @ 100% load,  

Latch Mode 

Short Circuit 

Hiccup Mode, Non-Latching 

(Auto-recovery when the fault is removed) 

Internal Fuse at L pin 

T3.15A 

Degree of Protection 

IP20 

Protection Against Shock 

Class I with PE* connection 

*PE: Primary Earth 

 

 

Содержание DRS-24V30W1NZ

Страница 1: ...IN rail power supply series is designed for industrial applications requiring highly reliable power supply within a tight space The Sync series operates with universal AC input range and offers full p...

Страница 2: ...test conditions for DC input Safety approval for DC input can be obtained upon request Output Ratings Characteristics Nominal Output Voltage 24Vdc Factory Set Point Tolerance 24Vdc 2 Output Voltage A...

Страница 3: ...ting Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 000 Meters 6 560 ft Shock Test Non Operating IEC60068 2 27 Half Sine Wave 50G for a duration of 11ms 3 times per direction 9 times in...

Страница 4: ...s Safety Entry Low Voltage SELV EN 60950 Electrical Safety TUV Bauart EN 60950 1 EN 62368 1 UL cUL recognized UL 60950 1 UL 62368 1 CSA C22 2 No 60950 1 File No E191395 CB Scheme IEC 60950 1 IEC 62368...

Страница 5: ...ia A1 2kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode3 2kV Differential Mode4 1kV Conducted IEC 61000 4 6 Level 3 Criteria A1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8...

Страница 6: ...meters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com July 2019 Rev 04 6 Block Diagram Device Description 1 Input terminal block connector 2 Output terminal blo...

Страница 7: ...Environment the device will run into Over Temperature Protection When activated power supply will latch off until the surrounding air temperature is lowered or the load is reduced as far as necessary...

Страница 8: ...ottom Each device is delivered ready to install Mounting No output power de rating across the entire input voltage range Dismounting Fig 2 1 Mounting Snap on the DIN rail as shown in Fig 2 1 1 Tilt th...

Страница 9: ...mm 0 39 inch to other units In case the adjacent device is a heat source the lateral distance will be 25mm 0 98 inch Note that the enclosure of the device can become very hot depending on the surround...

Страница 10: ...to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is the...

Страница 11: ...ernal feedback circuit fails The output voltage shall not exceed its specifications defined on Page 3 under Protections Power supply will latch off and require removal re application of input AC volta...

Страница 12: ...at any line voltage from 85 264Vac and set the PSU 1 and PSU 2 output voltage Step 2 Connect the power supply units PSU 1 and PSU 2 to Vin 1 Vin 2 respectively of the DRR 20N or 20A module shown on th...

Страница 13: ...tances in electrical and electronic equipment This product conforms to this standard Attention Delta provides all information in the datasheets on an AS IS basis and does not offer any kind of warrant...

Отзывы: