Operating Mode 

 

  Redundant Operation 

 

 

 

 

 

 

 

 

 

 

 

  Parallel Operation 

 

 

 

 

 

 

**The Signal GND in the DRR module is for the built-in LED and DC OK signals. The Output 

GND terminals from the two PSU’s do not need to be connected to the Signal GND terminal. 

 

Fig. 3   Redundant Operation Connection Diagram 

In order to ensure proper redundant operation for the 

power supply units (PSUs), the output voltage difference 

between the two units must be kept at 0.45~0.50V for 

these 24V supplies. Follow simple steps given below to 

set them up for the redundant operation: 

 

Step 1. 

Measure output voltage of PSU 1 and PSU 2. If PSU 1 is 

the master unit, then V

O

  of PSU 1 must be higher than 

PSU 2.  In order to set  the output voltage, individually 

connect each power supply to 50% of rated load at any 

line voltage from 85-264Vac, and set the PSU 1 and PSU 

2 output voltage. 

 

Step 2. 

Connect the power supply units PSU 1 and PSU 2 to Vin 

1 & Vin 2, respectively, of the DRR-20N (or 20A) module 

shown on the right of above diagram. 

 

Step 3. 

Connect the system load to V

out

. Please note that output 

voltage V

out

 from DRR module will be = V

O

 (output voltage 

of power supply) – V

drop

* (in DRR module). 

 

*Vdrop will vary from 0.60V  to 0.90V (Typical 0.65V) depending on the 

load current and surrounding air temperature. 

Fig. 4   Parallel Operation Connection Diagram 

 

The power supply units (PSUs) can also be used for 

parallel operation in order to increase the output power. 

The difference in output voltage between the two units 

must be kept to within 25mV of each other. This 

difference must be verified with  the same output load 

connected independently to each unit. 
Parameters such as EMI, inrush current, leakage current, 

PARD, start up time will be different  from those on the 

datasheet, when two units are connected in parallel. The 

user will need to verify that any differences will still allow 

the two power supplies connected in parallel will work 

properly in their product/application. 

 

Содержание DRS-24V30W1NZ

Страница 1: ...IN rail power supply series is designed for industrial applications requiring highly reliable power supply within a tight space The Sync series operates with universal AC input range and offers full p...

Страница 2: ...test conditions for DC input Safety approval for DC input can be obtained upon request Output Ratings Characteristics Nominal Output Voltage 24Vdc Factory Set Point Tolerance 24Vdc 2 Output Voltage A...

Страница 3: ...ting Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 000 Meters 6 560 ft Shock Test Non Operating IEC60068 2 27 Half Sine Wave 50G for a duration of 11ms 3 times per direction 9 times in...

Страница 4: ...s Safety Entry Low Voltage SELV EN 60950 Electrical Safety TUV Bauart EN 60950 1 EN 62368 1 UL cUL recognized UL 60950 1 UL 62368 1 CSA C22 2 No 60950 1 File No E191395 CB Scheme IEC 60950 1 IEC 62368...

Страница 5: ...ia A1 2kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode3 2kV Differential Mode4 1kV Conducted IEC 61000 4 6 Level 3 Criteria A1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8...

Страница 6: ...meters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com July 2019 Rev 04 6 Block Diagram Device Description 1 Input terminal block connector 2 Output terminal blo...

Страница 7: ...Environment the device will run into Over Temperature Protection When activated power supply will latch off until the surrounding air temperature is lowered or the load is reduced as far as necessary...

Страница 8: ...ottom Each device is delivered ready to install Mounting No output power de rating across the entire input voltage range Dismounting Fig 2 1 Mounting Snap on the DIN rail as shown in Fig 2 1 1 Tilt th...

Страница 9: ...mm 0 39 inch to other units In case the adjacent device is a heat source the lateral distance will be 25mm 0 98 inch Note that the enclosure of the device can become very hot depending on the surround...

Страница 10: ...to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is the...

Страница 11: ...ernal feedback circuit fails The output voltage shall not exceed its specifications defined on Page 3 under Protections Power supply will latch off and require removal re application of input AC volta...

Страница 12: ...at any line voltage from 85 264Vac and set the PSU 1 and PSU 2 output voltage Step 2 Connect the power supply units PSU 1 and PSU 2 to Vin 1 Vin 2 respectively of the DRR 20N or 20A module shown on th...

Страница 13: ...tances in electrical and electronic equipment This product conforms to this standard Attention Delta provides all information in the datasheets on an AS IS basis and does not offer any kind of warrant...

Отзывы: