29
C1
pickup setpoint (current THD
exceeding this value, alarm
generated)
0.000~99999.999
Float
%
4
R / W
C2
C3
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W
C4
dropout setpoint (current THD
lower than this value (kW), alarm
cleared)
0.000~99999.999
Float
%
4
R / W
C5
C6
dropout time delay (restoration
delayed)
0~99
byte
s
2
R / W
Alarm - Phase Loss
C7
Alarm Enable
0: Disable
1: Enable
byte
1
R / W
C8
pickup setpoint (phase lower than
this value, alarm generated)
0.000~99999.999
Float
V
4
R / W
C9
CA
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W
CB
dropout setpoint (phase
exceeding this value, alarm
cleared)
0.000~99999.999
Float
V
4
R / W
CC
CD
dropout time delay (restoration
delayed)
0~99
byte
s
2
R / W
Alarm - Over DUI
CE
Alarm Enable
0: Disable
1: Enable
byte
1
R / W
CF
pickup setpoint (DUI exceeding
this value, alarm generated)
0.000~99999.999
Float
kW
4
R / W
D0
D1
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W
D2
dropout setpoint (DUI lower than
this value, alarm cleared)
0.000~99999.999
Float
kW
4
R / W
D3
D4
dropout time delay (restoration
delayed)
0~99
byte
s
2
R / W
Alarm - Over EUI
D5
Alarm Enable
0: Disable
1: Enable
byte
1
R / W
D6
pickup setpoint (EUI exceeding
this value, alarm generated)
0.000~99999.999
Float
kWh
4
R / W
D7
D8
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W
D9
dropout setpoint (EUI lower than
this value, alarm cleared)
0.000~99999.999
Float
kWh
4
R / W
DA
DB
dropout time delay (restoration
delayed)
0~99
byte
s
2
R / W
Alarm - Meter Reset
DC
Alarm Enable
0: Disable
1: Enable
byte
1
R / W
Alarm - Phase Rotation
DD
Alarm Enable
0: Disable
1: Enable
byte
1
R / W