25
4C
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W
4D
dropout setpoint (voltage
exceeding this value (V), alarm
cleared)
0.000~99999.999
Float
V
4
R / W
4E
4F
dropout time delay (restoration
delayed)
0~99
byte
s
2
R / W
Alarm - Over Voltage Unbalance
50
Alarm Enable
0: Disable
1: Enable
byte
1
R / W
51
pickup setpoint (voltage
unbalance exceeding this value
(V), alarm generated)
0.000~99999.999
Float
%
4
R / W
52
53
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W
54
dropout setpoint (voltage
unbalance lower than this value
(V), alarm cleared)
0.000~99999.999
Float
%
4
R / W
55
56
dropout time delay (restoration
delayed)
0~99
byte
s
2
R / W
Alarm - Over Current Unbalance
57
Alarm Enable
0: Disable
1: Enable
byte
1
R / W
58
pickup setpoint (current
unbalance exceeding this value
(A), alarm generated)
0.000~99999.999
Float
%
4
R / W
59
5A
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W
5B
dropout setpoint (current
unbalance lower than this value
(A), alarm cleared)
0.000~99999.999
Float
%
4
R / W
5C
5D
dropout time delay (restoration
delayed)
0~99
byte
s
2
R / W
Alarm - Over Active Power
5E
Alarm Enable
0: Disable
1: Enable
byte
1
R / W
5F
pickup setpoint (active power
exceeding this value (kW), alarm
generated)
0.000~99999.999
Float
kW
4
R / W
60
61
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W
62
dropout setpoint (active power
lower than this value (kW), alarm
cleared)
0.000~99999.999
Float
kW
4
R / W
63
64
dropout time delay (restoration
delayed)
0~99
byte
s
2
R / W
Alarm - Over Reactive Power
65
Alarm Enable
0: Disable
1: Enable
byte
1
R / W
66
pickup setpoint (reactive power
exceeding this value (kVAR),
alarm generated)
0.000~99999.999
Float
kVAR
4
R / W
67
68
pickup time delay (triggering
delayed)
0~99
byte
s
2
R / W