User and Installation Manual for DE212-1S Wired Deadman 

 

D

ELTA  

RCS

 

AS 

 

Page 5 of 17 

 

 

Document: 02002 

     NOTES:

 

 

 

Input voltage should be 12 or 24VDC.  Max 35VDC 

 

All outputs gives 12/24V out when activated, max 3,5A per output, total load: 5A. 

 

Note that the potential between the minus pole and ground/GND, must not be greater than 50VDC/AC peak. 

 

Deadman cable input has no polarity requirements. 

 

The warning outputs operates as follows: when the deadman function is activated, the warning light is 
activated at the same time. When 30 seconds remain of the timer period, the warning light output change 
from a steady signal to an intermitted signal during the last 30 seconds of the time period. During the 
intermitted signal, the beeper warning goes active, with a steady signal as long as the warning light signal is 
intermitted. 

 

2.2

 

C

HANGE OF FUNCTIONS BY 

SW2. 

 

NOTE:  Switch SW2 is located on the printed circuit board inside the control unit. 

The state of all 4 single switches of SW2 will be read, stored and activated by the control units 
microprocessor if the CODE-button on the front is pressed and hold for more than 3 sec. when 
switching on the control unit.  
After this 3 sec. the green 

ON

 led on the front turns on (lights up), indicating that the process 

is finished successful. 
When the control unit is connected to the power supply, this SW2-reading-process can also 
easily be initiated by pulling out the fuse F1/5A and push it back into its socked. 

 

 

Deadman function, with or without timer.  

This selection will done by SW2-1. 
For timed deadman, set SW2-1 to ON. For no timer, set F2-1 to OFF 

 

 

Deadman override enabled/disabled 

To enable the deadman override input set SW2-3 to ON.  
To disable the deadman override input, set SW2-3 to OFF.  

.

 

 

 

Type of handswitch, failsafe / not failsafe 

The CU212-1S can operate with other handswitches as the failsafe CB212-1S. 
If a handswitch with an ordinary ON/OFF switch is used, (not failsafe) the control unit CU212-1S has to be set 
for NOT FAILSAFE operation: 
To set the control unit for using a failsave CB212-1S handswitch, set SW2-4 to ON  
To set the control unit for using a NON-FAILSAFE handswitch, set SW2-4 to OFF 

 

NOTE: The external STOP input is always enabled. 

 

 

Standard factory setting of SW2 switches: 

 

 

 

 

SW2

 

OFF    ON

 

1

 

2

 

3

 

4

 

 

1.

Deadman timer     enabled/disabled 

2.

Not in Use 

3.

Deadman override input     enabled/disabled 

4.

Type of Handswitch     Failsafe/Not failsafe 

Содержание DE212 GLOBAL

Страница 1: ...P O Box 1065 S ndre Kuller d 4A Web site www deltarc no Last revision 18 08 2017 N 3204 Sandefjord E mail hello deltarc no Norway Delta DE212 Failsafe Wired Deadman Control for Aero Plane Refuelling T...

Страница 2: ...3 INSTALLING THE CONTROL UNIT 6 2 4 CABLE CONNECTION TO HANDHELD UNIT 6 3 OPERATION 7 3 1 UNIT DESCRIPTION 7 3 2 FUNCTION DESCRIPTION 8 3 3 MAINTENANCE 10 4 SPARE PARTS 10 5 WARRANTY CONDITIONS 11 6 T...

Страница 3: ...mote position The DE212 has a built in timer system with timeout warning outputs for light and beeper The standard timer is set to 2 minutes with the warning signals 30 seconds before the refuelling w...

Страница 4: ...onnected as described See figure below Connections to the PCB in the control unit P1 Output Signals 1 DC output signal to horn beeper 2 Warning light signal 3 Not in use Do not connect 4 Deadman outpu...

Страница 5: ...hold for more than 3 sec when switching on the control unit After this 3 sec the green ON led on the front turns on lights up indicating that the process is finished successful When the control unit...

Страница 6: ...board and connect the cables to the connectors while they are free to move and easy to keep in the right position When all cables are connected replace the connectors to the printed circuit board and...

Страница 7: ...consists of the following parts CU212 1S control unit for installation in the drivers cabin CB212 1S handheld switch Connection box optional not included in the delivery 14m coiled cable not included...

Страница 8: ...e design telling that the system will stop if something goes wrong That is for instance if the cable short circuits This will immediately shut down the fuelling The wired deadman is normally delivered...

Страница 9: ...it is powered this output is active supplying 12 24V When the STOP button is activated this output is switched off If the cable is shorted this output is also switched off Warning light output Is acti...

Страница 10: ...equipment housing is damaged Dirty equipment should therefore always be cleaned As a rule the equipment should be sent to service as quick as possible when such damages occurs without waiting till the...

Страница 11: ...t the customer s location there will be charges for cost of travelling accommodation and dieting conforming to the government s assertions There will also be an additional charge of 50 of travelling t...

Страница 12: ...arning light output active during operation of the deadman Beeper warning output STOP output When control unit is powered this output is active output is12 24V When STOP is detected this output is swi...

Страница 13: ...User and Installation Manual for DE212 1S Wired Deadman DELTA RCS AS Page 13 of 17 Document 02002 6 4 DIMENSIONS 6 4 1Control Unit All dimensions in mm...

Страница 14: ...User and Installation Manual for DE212 1S Wired Deadman DELTA RCS AS Page 14 of 17 Document 02002 6 4 2 Handswitch All dimensions in mm...

Страница 15: ...2 1S Wired Deadman DELTA RCS AS Page 15 of 17 Document 02002 6 4 3 Wall mount for Handswitch All dimensions in mm Delta RC AS AS reserves the right to change the specifications and upgrade its product...

Страница 16: ...thing powered by an electrical source e g from a power socket or a battery The batteries should be disposed properly at a battery recycling facility The housings should be disposed as general waste Pl...

Страница 17: ...Kuller d 4A E mail hello deltarc no NO 3204 Sandefjord Norway www deltarc no Delta RC AS reserves the right to make changes without further notice to the product to improve reliability functions and d...

Отзывы: