CANopen Communication Module DVPCOPM-SL
Required settings in DVPCOPM-SL:
Parameter
Setting
Explanation
Node address
01
Set the node address of DVPCOPM-SL to “01”.
Baud rate
1 Mbps
Set the communication speed between DVPCOPM-SL and
bus to “1 Mbps”.
Required settings in IFD9503:
Parameter
Setting
Explanation
Node address
02
Set the node address of IFD9503 to “02”.
Baud rate
1 Mbps
Set the communication speed between IFD9503 and bus to
“1 Mbps”.
Required settings in VFD-B AC motor drive:
Parameter
Setting
Explanation
02-00
04
The main frequency is operated by RS-485 interface.
02-01
03
The running command is operated by communication
interface. Operation by keys is valid.
09-00
01
Communication address of VFD-B: 01
09-01
03
Baud rate: 38,400 bps
09-04
03
Modbus RTU mode, format <8, N, 2>
Devices in PLC:
Explanation
PLC device
Content
15 14 13 12 11 10 9
8
7
6
5
4 3 2 1 0
D6250
0101Hex
ReqID = 01Hex
Command = 01Hex
D6251
0004Hex
Reserved
Size = 04Hex
D6252
0102Hex
Type = 01Hex
MAC ID = 02Hex
D6253
2021Hex
High byte of index = 20Hex
Low byte of index = 21Hex
SDO request
message
editing area
D6254
0004Hex
Reserved
Sub index = 04Hex
D6000
0101Hex
ReqID = 01Hex
Status = 01Hex
D6001
0006Hex
Reserved
Size = 06Hex
D6002
4B02Hex
Type = 4BHex
MAC ID = 02Hex
D6003
2021Hex
High byte of index = 20Hex
Low byte of index = 21Hex
D6004
0004Hex
Reserved
Sub index = 04Hex
SDO response
message
editing area
D6005
0100Hex
Datum 1= 01Hex
Datum 0 = 00Hex
0100Hex in D6005 refers to the actual output frequency of the AC motor drive is 2.56Hz.
PLC
program
M1002
ZRST
D6250
D6281
ZRST
D6000
D6031
Reset response message editing area
and request message editing area.
DVP-PLC Operation Manual