HD50
- 29 -
V1.4
Coils
- Read/Write parameters
Address Type
Coil description
1
b
Logging status: 0=active, 1=inactive
2
b
Logging mode: 0=non cyclic, 1=cyclic
3
b
Set 1 to delete the device logging memory. Bit zeroing is automatic.
4
b
Buzzer activation in case of measurement alarm: 0=no, 1=yes
9 b
Protection of configuration with password: 0=no, 1=yes
Changing the parameter requires the Administrator password (see Holding
Register 10036).
Input Registers
- Read-only parameters
Address Type
Input Register description
Measured values and status of measurement alarms
0 SW
T
EMPERATURE
with
NTC10K
sensor of channel
1
in the set measurement
unit (x10).
1 B
Alarm for temperature with NTC10K sensor of channel 1:
0=OFF, 1= lower threshold alarm, 2= higher threshold alarm
2 SW
R
ELATIVE
H
UMIDITY
in % (x10).
3 B
Relative humidity alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
4 SW
D
EW
P
OINT
in the set measurement unit (x10).
5 B
Dew Point alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
6 SW
P
ARTIAL VAPOR PRESSURE
in hPa (x100).
7 B
Partial vapor pressure alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
8 SW
M
IXING
R
ATIO
in g/Kg (x10).
9 B
Mixing ratio alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
10 SW
A
BSOLUTE
H
UMIDITY
in g/m
3
(x10).
11 B
Absolute humidity alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
12 SW
W
ET
B
ULB TEMPERATURE
in the set measurement unit (x10).
13 B
Wet bulb temperature alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
16 SW
T
EMPERATURE
with
NTC10K
sensor of channel
2
in the set measurement
unit (x10).
17 B
Alarm for temperature with NTC10K sensor of channel 2:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
20 SW
I
LLUMINANCE
in lux (low range, models HD50...I...).
21 B
Illuminance (low range, models HD50...I...) alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
24 SW
A
TMOSPHERIC
P
RESSURE
in the set measurement unit (the multiplier de-
pends on the set unit).
25 B
Atmospheric pressure alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
32 SW
CO
2
in ppm.
33 B
CO
2
alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
50 SW
T
EMPERATURE
with
NTC10K
sensor of channel
3
in the set measurement
unit (x10).