Keys
Function
ENTER
E
+ DOWN (press for min 3 secs!)
Enter or exit QUICKSET programming mode
UP , DOWN , NEXT
Increase/decrease and move left the blinking digit
UP + DOWN
“GET LEVEL”
–
display actual level measured by the DMSP400/500
ENTER
E
Save readout and step to the next screen
NEXT + UP
Quit Current Output Scaling without saving the modifications (CANCEL))
NEXT + DOWN
Display of the DEFAULT value.
Screens
Actions
A
P
:
x
x
y
y
AP
plication
xx
= select “EU” (European) for metric or “US” for US engineering units
(Use
UP
/
DOWN
keys)
yy= indicating “Li” for liquids
DEFAULT: EU
Programming of this parameter will result in loading the factory default
with the corresponding engineering units.
H
:
x
x
x
x
H
=
xxxx
maximum measuring distance
–
Distance between transducer face and tank bottom
Manual: set value
(
Use UP
/
DOWN
/
NEXT
keys)
and save it
(by
ENTER
E
)
Automatic: use the “GET LEVEL” function
(
UP
+
DOWN
)
to obtain actual measured value with level in tank or a fixed
target, i.e. wall. (“GET LEVEL” functions only if ECHO LED is lit) and save it as above.
DEFAULT: maximum measuring distance [m], see Technical Data Table
4
:
x
x
x
x
4
mA
xxxx
–
level value
assigned to 4 mA current output
Manual: set level value
(by
UP
/
DOWN
/
NEXT
keys)
and save it
(by
ENTER
E
)
Automatic: use the “GET LEVEL” function
(
UP
+
DOWN
)
to display the actual measured value with level in tank or a
fixed target, i.e. wall. (“GET LEVEL” functions only if ECHO
LED is lit) and save it as above.
DEFAULT: 0 m (0%, Empty tank)