Chapter 4 Parameter Settings
|
DD Series
4-14
06 Protection and Special Parameters
This parameter can be set during operation.
Parameter
Explanation
Settings
Factory
Setting VF VFP SVC FO
C
FO
C
06.00 Software Braking Level
350.0~450.0Vdc 380.0
○
○
○ ○ ○
06.01 ED Setting of Brake
Resistor
0~100% 50
○
○
○ ○ ○
06.02 Current Boundary
0
~
250%
200
○ ○
06.03 Forward Motor Torque Limit 0
~
250%
200
○ ○
06.04 Forward Regenerative
Torque Limit
0
~
250%
200
○ ○
06.05 Reverse Motor Torque Limit 0
~
250%
200
○ ○
06.06 Reverse Regenerative
Torque Limit
0
~
250%
200
○ ○
06.07 Emergency/Force Stop
Deceleration Method
0:Coast to stop
1: Decelerate by 1st decel. time
2: Decelerate by 2nd decel. time
3:By Pr.05.33 setting
3
○
○
○ ○ ○
06.08 Low Voltage Level
160.0~270.0Vdc 180.0
○
○
○ ○ ○
06.09 High Temperature
Overheat Warning (OH)
0.0~110.0
℃
85.0
○
○
○ ○ ○
06.10
Action after door
re-open/re-close
Bit 0=0:Not detecting incorrect
open/close limit
Bit 0=1:Detects incorrect open/close
limit
Bit 1=0:Door re-open when door close
error occur
Bit 1=1:Door will not re-open when door
close error occur
Bit 2=0:Enable S-Curve when door
re-open
Bit 2=1:Disable S-Curve when door
re-open
Bit 3=0: When door open complete, will
not reset door position to
100.0%.
Bit 3=1:When door open complete,
resets door position to 100.0%
Bit4=0 Door opening in position not
supported, limited signal will be
output after the torque is
enabled.
Bit4=1 Door opening in position is
supported, limited signal will be
output after the torque is
enabled.
Bit5=0 Reset LVn error automatically,
MO terminal sends error signal
Bit5=1 Reset LVn error
automatically, MO terminal
sends error signal
2
○
○
○ ○ ○
Содержание VFD-DD Series
Страница 1: ......
Страница 13: ...Chapter 1 Introduction DD Series 1 7 ECMD B9160GMS...
Страница 32: ...Chapter 4 Parameter Settings DD Series 4 8...