Required Protective Devices and Cable Selection 

    Refer to the following table on recommended cables and upstream protection: 

 

Model 

Rated Input Cable   

Rated Output Cable

 

Upstream Circuit-Breaker 

6 KVA 

8AWG or 8mm

2

 

8AWG or 8mm

2

 

D curve – 40A 

12 KVA 

6AWG or 14mm

2

 

6AWG or 14mm

2

 

D curve – 63A 

 

Selection of Conduit and Bushing 

According to National Electrical Code, install all the wiring with suggested suitable conduit and 

bushing as below. 

z

  Conduit: Flexible metal conduit sized one inch. 

z

  Bushing: Overall diameter is 40.5mm, height is 13.1mm. 

 

Input and Output Connection 

When connecting the cable, please note that: 

1. Before connecting, turn off the UPS and cut off AC power and battery.   

2. Ensure the cable is fitted. The minimum tightening torque shall not be less than 35 lbs with a 

cable sleeve & secured by the connector clamp. 

3. 

Connect the EARTH wire to the terminal marked with 

“ 

 ” . 

 

Connective Methods of Input and Output 

 
1. Output 

1

‡

: (For 6KVA and 12KVA) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

Содержание Amplon Family

Страница 1: ...www deltapowersolutions com Delta UPS Amplon Family User Manual The power behind competitiveness N Series Single Phase 6 12 kVA...

Страница 2: ...Any disposition duplication dissemination reproduction modi cation translation extraction or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta Given...

Страница 3: ...4 4 HANDLING 13 5 OPERATION 14 5 1 POWER ON OFF INVERTER 14 5 2 LCD FUNCTION SELECTION SWITCH 16 5 3 PARAMETER SET UP MODE 17 5 4 OPERATION ON BYPASS VOLTAGE BEYOND ALLOWABLE RANGE 19 5 5 OVERLOAD AND...

Страница 4: ...k of a possible electrocution is possible when the battery is connected to the UPS Therefore do not forget to disconnect the batteries before any service is to be done on the UPS To disconnect remove...

Страница 5: ...isk of electric shock and chemical hazard The following precaution should be observed when working on batteries Remove watches rings or other metal objects Use only tools with insulated handles The co...

Страница 6: ...provide detailed information on operation status z Manual and static bypass switch forms Allowance for switching to the main power supply z Static bypass supply circuit incorporates functions such as...

Страница 7: ...ON LINE and ECONOMY modes pressing the up button for more than 3 seconds can detect the battery capacity NOTE If the UPS is in alarm status pressing the up or down button for more than 3 seconds can d...

Страница 8: ...5 2 3 REAR CONTROL PANEL 6KVA 11 10 6 1 4 2 5 8 7 9 3 EMERGENCY 240VDC 20A AC BREAKER INPUT MANUAL BYPASS POWER OFF CONTACT DRY RS 232 SNMP BATT NO...

Страница 9: ...6 12KVA MANUAL BYPASS 240VDC 40A RS 232 CONTACT EMERGENCY DRY POWER OFF SNMP BATT NO 11 9 8 7 4 1 6 10 5 3 2...

Страница 10: ...onnects to external battery cabinet to extend the backup time 5 AC INPUT BREAKER Provides safe protection for UPS AC input 6 EXHAUST FANS For cooling air ventilation of UPS 7 REMOTE EMERGENCY POWER OF...

Страница 11: ...5 Hz Programmable 3 5 Input Protection Circuit Breaker 40A 1 pole x 1 63A 1 pole x 1 4 Output 4 1 Output Voltage RMS Voltage 120V 220Vac single phase Static Regulation r 2 4 2 Harmonic Distortion 5 4...

Страница 12: ...4200W 3 Minutes 8400W 6 Operation 6 1 Transfer Time On line Mode Main Power Failure 0ms Main Power Recover 0ms Inverter To Bypass 1ms Bypass To Inverter 1ms Economy Mode Main Power Recover 0ms Inverte...

Страница 13: ...G 365 7LB Battery Cabinet Weight 180KG 396LB 12 Environment 12 1 Ambient Operating Temperature 0o C 40 o C 32 o F 104 o F 12 2 Ambient Storage Temperature 20 o C 40 o C 4 o F 104 o F 12 3 Relitive Hum...

Страница 14: ...s 20qC to 60qC without batteries 20qC to 45qC with batteries for a short period Maximum period for battery storage 6 months at 20qC or 3 months at 30qC Eight hours of charging time is needed when the...

Страница 15: ...the wiring with suggested suitable conduit and bushing as below z Conduit Flexible metal conduit sized one inch z Bushing Overall diameter is 40 5mm height is 13 1mm Input and Output Connection When c...

Страница 16: ...er to Fig 1 2 or Fig 1 3 z The UPS should always have a clearance space of 300mm at the rear and 100mm on its side Refer to Fig 4 Fig 1 Fig 2 Fig 3 Fig 4 First change the direction and revolve screw p...

Страница 17: ...UPS starts diagnostic test and shows the results on the back lit LCD display as below DIAGNOSIS MODE AC START BATTERY START DIAGNOSIS MODE FREQ OUT XXHZ DIAGNOSIS MODE INPUT XXXV XXHZ DIAGNOSIS MODE R...

Страница 18: ...hed to BYPASS mode z If the UPS is in backup mode the message UPS OFF WAITING will be displayed on LCD about thirty seconds then disappear z Before removing the battery connect wire please wait until...

Страница 19: ...T KEY PRESS THE SELECT KEY CHRG XXXV FLOAT BOOST PRESS THE SELECT KEY PRESS THE SELECT KEY IN XXXV XX XHz ECONOMY MODE ECONOMY MODE ECONOMY MODE ECONOMY MODE ECONOMY MODE ECONOMY MODE OPERATION IN ON...

Страница 20: ...e t i n i t i a l S e l e c t e c o n o m y m o d e R e t u r n t o s e t i n i t i a l S e l e c t o u t p u t f r e q u e n c y R e t u r n t o s e t i n i t i a l UPS SET UP EXIT ENTER OUTPUT VOLTA...

Страница 21: ...5Ah 16 090Ah 21 140Ah 26 190Ah EXTEND NONE SCROLL SELECT EXTEND BATTERY SCROLL SELECT EXTEND 010Ah SCROLL SELECT EXTEND 015Ah SCROLL SELECT EXTEND 190Ah SCROLL SELECT EXTEND 200Ah SCROLL SELECT TO UPS...

Страница 22: ...XXX X XXKW 1 minute 125 150 OVERLOAD 125 LOAD XXX X XXKW 30 seconds 150 OVERLOAD 150 LOAD XXX X XXKW Immediate Shutdown Operation Condition LCD Display Message Extended Overload OVERLOAD XXX SHUT DOWN...

Страница 23: ...the AC input power is directly supplied to the load CAUTION Activate manual bypass switch only when the UPS is in BYPASS mode BYPASS BYPASS NORMAL NORMAL z STEP 1 Turn off the inverter power to switc...

Страница 24: ...pin 2 5 or pin 4 5 or pin 4 3 then the UPS will be powered off NOTE This port must not be connected to the Telecom Port z Load level z Battery status z Battery level z UPS mode z Input voltage z Outp...

Страница 25: ...ry contact table Pin State Pin 8 3 Pin 1 3 Pin 6 3 Pin 5 3 Pin 2 3 Normal Open Open Open Back up Close Low Battery Close Fault Close Bypass Close Open Inverter Open Close Pin Assignment Fig 5 2 NOTE m...

Страница 26: ...MP network interface is a powerful tool for remote control and UPS monitoring NOTE For more information on SNMP card optional contact your local dealer MANUAL BYPASS 240 VDC40A RS 232 CONTACT EMERGENC...

Страница 27: ...PACK When the UPS is connected with Delta s standard battery packs you can detect the total battery capacity by linking the UPS to the battery pack NOTE This function can detect up to a maximum of tw...

Страница 28: ...ce or irresistible force i e war re natural disaster etc and this warranty also expressly excludes all inci dental and consequential damages Maintenance service for a fee is provided for any damage ou...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Отзывы: