8
3. TECHNICAL SPECIFICATION
Model 6KVA
12KVA
1. Power
1.1 Power (VA)
6000VA
12000VA
1.2 Power (W) PF=0.7
4200W
8400W
2. Output Waveform
Sine wave
3. Input
3.1 Input Voltage
220Vac, single phase
3.2 Input Current
27.3A
54.5A
- Inrush Current
200A
- Power Factor
!
0.99 (At Normal Line and Full Load)
3.3 Efficiency (Full Resistance Load)
- On line Mode (AC to AC)
88% (Full linear load)
- Economy Mode
94% (Full linear load)
3.4 Input Frequency
50/60Hz±0.5,1, 2, 3, 4, 5 Hz (Programmable)
3.5 Input Protection Circuit Breaker
40A (1 pole x 1)
63A (1 pole x 1)
4. Output
4.1 Output Voltage
- RMS Voltage
120V/220Vac, single phase
- Static Regulation
r
2
4.2 Harmonic Distortion
5%
4.3 Overload Capability
Љ
102% Continuous
102%~125%: 1 Minute
125%~150%: 30 Seconds
!
150%: Immediate
4.4 Overload Release
90
r
5
(Rated Load)
4.5 Inverter Short Circuit Protection Current
90A 150A
4.6 Short Circuit Protection
Shutdown and no output
4.7 Output Frequency
50/60Hz
r
0.5Hz (Battery mode)
4.8 Output Protection Circuit Breaker
- Bypass (Outside Installation Capacity)
40A(1pole*1) 63A(1pole*1)
- Inverter
Electronic protection
4.9 Crest Factor
2.7:1