Delta Lighting Controller (GE Lighting) DLC-G1212 (Rev 1.3) Installation & Application Guide
Mounting
The GE Lighting Controller is designed for mounting quickly and easily in a number of locations, usually
within one of several sizes of GE relay enclosures. Ensure the controller itself is a safe distance away or in
some other way protected from relief valves and other water sources.
Input & Output Wiring
Input and output wiring on the Delta GE Lighting Controllers is very simple. GE relays plug securely on to
the 5-pin connectors provided.
24V Half Wave Power (YELLOW)
STATUS (YELLOW)
OFF (BLACK)
ON (RED)
24V Half Wave Power (BLUE)
DLC-G1212
- NET
1
+
P
O
W
ER
IN
24~
G
N
D
24
~
G
N
D
R
X
T
X
- NET
2
+
TX
RX
RE
L
A
Y
1
SW
E
EP IN
PU
T
ON
OFF
G
N
D
POW
E
R
O
U
T
GN
D
BI1
SWITCH 3
RE
L
A
Y
2
SWITCH 2
RE
L
A
Y
3
RE
L
A
Y
4
SWITCH 4
SWITCH 5
SC
A
N
PW
R
RS
O
N
OFF
G
N
D
R
S
O
N
OF
F
G
N
D
R
S
O
N
OFF
G
N
D
PILOT
ON
OFF
GND
(FRONT VIEW)
(BACK VIEW)
GE RS3xP LOW VOLTAGE
LIGHT SWITCH WITH PILOT
GE RR9
RELAY
GND
ON
PILOT
OFF
Power
The GE Lighting Controller requires a 24 VAC @ 50 VA power supply – this includes GE relay power
requirements – typically an isolated Class II transformer. More than one controller – not including DCUs or
V2 products – may be connected to the same transformer, providing the transformer is properly sized,
(including line losses), and polarity is observed between controllers (in regards to 24~ and GND). The
transformer must
ONLY
be used to provide power to the controller and devices powered through its outputs.
Auxiliary field devices (i.e., 4-20 mA devices) that don’t use ½ wave rectification must be powered
separately.