Delta Lighting Controller (GE Lighting) DLC-G1212 (Rev 1.3) Installation & Application Guide

 

Network Topology 

 
Delta’s GE Lighting Controllers are designed to be installed in a system of V3.22 controllers, and are fully 
capable as peer-to-peer controllers on a BACnet MS/TP network as Subnet devices, typically with one 
System device (DCU or otherwise). 
 

DCU/DSC

(System Device)

BACnet (MS/TP) - Level 3 Network (Subnet)

DLC

(Subnet

Device)

TRM

DLC

(Subnet

Device)

TRM

Level 4

Network

(LINKnet)

 16x16 Controller
 12x12 Controller
 12x8 Controller
 6x6 Controller
 Room Controller
 VAV/VVT Controller
 Lighting Controller
 BACstat I
 BACstat II

  (with or without I/O)

 Input Field Modules

Subnet Devices

 DSC-1616EX [DCU]
 DSC-1616(H/E)
 DSC-1212(H/E)
 DSC-1280(H/E)
 DSC-T305

System Devices

RS-485

NET1

NET2

NET1

NET2

RS-232

 BACstat I(DNS-14)
 BACstat II (DNS-24)

LINKnet Devices

TRM

Level 4

Network

(LINKnet)

TRM

LINKnet Notes:

1.  Ensure you use the recommended
     balanced cable.
2.  Ensure the cable is installed as a
     daisy-chain from one device to the
     next. (1000' or 300m maximum).
3.  Ensure you install MS/TP terminator
     boards when you have more than 1 or
     2 devices.
4.  Depending on the controller, up to 12
     devices are supported on a LINKnet
     network, with limitations on how many
     of these may have I/O.  (Refer to
     the Technical Reference Manual.)

ORCAview

OWS

DFM

Ethernet Note:

If the DCU or DSC has Ethernet capability, it may exist on an
Ethernet network with other controllers in the same building, on which
the ORCAview OWS could reside as well (instead of PTP).

PTP

MS/TP Notes:

1.  Ensure you use the recommended balanced cable.
2.  Ensure the cable is installed as a daisy-chain from one device to
     the next (4,000' or 1220m maximum).
3.  Ensure you install an MS/TP terminator board (TRM-768) on each
     end of each MS/TP network.
4.  The maximum nodes per MS/TP network is 50 without a repeater,
     or up to 99 with at least one repeater (RPT-768).

Network Diagram 

 (with V3.22 Firmware)

 

 
 

Network Communications Setup 

 
The GE Lighting Controller communicates on a BACnet MS/TP network at a default speed of 76,800 bps.  
Refer to the 

ORCAview Technical Reference Manual

 for further detail on configuring the BACnet MS/TP 

network or changing baud rates, etc. 
 

 

Page 10 of 15

 

 

Document Edition 1.5

 

Содержание DLC-G1212

Страница 1: ...ching up to 12 GE lighting relay zones the GE Lighting Controller is ideal for mounting in various GE relay enclosures for both new and retrofit construction projects The controller also includes a bu...

Страница 2: ...3 22 Firmware Software Important Information The capabilities of the GE Lighting Controller are dependent on the firmware version that is loaded The following is not intended to be comprehensive but s...

Страница 3: ...ing Relay Outputs Maximum 4 GE Relays per output RR7x 3 wire Relays Control Only with No Status Delta PN 47101 Relays with no feedback RR9x 5 wire Relays Control and Status including LED Indication De...

Страница 4: ...d jumpers or Software Setup DIP switch MAC Address Range 0 to 99 per network segment Software Address Range As per the BACnet standard Supports DNA Delta s intuitive addressing scheme Size Controller...

Страница 5: ...E L 9 R E L 1 0 SWITCH 9 SWITCH 10 R E L 1 1 R E L 1 2 SWITCH 11 SWITCH 12 SC AN P W R RS O N OF F G ND RS O N OF F G ND RS O N OF F G ND RS O N OF F G ND RS O N OF F G ND RS O N OF F G ND RS O N OF...

Страница 6: ...ing data through the port Inputs IP1 IP12 Input Status Indicators A corresponding red LED flickers when the associated binary input is in the active state Sweep Output OP13 Sweep Output Signal Indicat...

Страница 7: ...mapped into the Subnet portion of its address inheriting other portions of its BACnet address when DNA is enabled DNA DERIVED NETWORK ADDRESSING DNA Derived Network Addressing DNA which works in conj...

Страница 8: ...ON OFF GND POWER OUT GND BI1 SWITCH 3 RELAY 2 SWITCH 2 RELAY 3 RELAY 4 SWITCH 4 SWITCH 5 SCAN PWR RS ON OFF GND RS ON OFF GND RS ON OFF GND PILOT ON OFF GND FRONT VIEW BACK VIEW GE RS3xP LOW VOLTAGE...

Страница 9: ...ropagation of 66 or higher Topology Ensure the MS TP network cable is installed as a daisy chain from one device to the next Max Nodes The maximum number of devices per MS TP network without any repea...

Страница 10: ...ext 1000 or 300m maximum 3 Ensure you install MS TP terminator boards when you have more than 1 or 2 devices 4 Depending on the controller up to 12 devices are supported on a LINKnet network with limi...

Страница 11: ...ed to represent two things Relay Output i e command Relay Status including when controlled by associated hardwired lighting switches E g To look for the Status Feedback Value the property you should u...

Страница 12: ...BO object to a non feedback condition To set the Binary Output BO object to a non feedback condition 1 Open the BO associated with the RR7 relay 2 Under the Device Tab in the Module section there is a...

Страница 13: ...CC Compliance Information This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reas...

Страница 14: ...erconnected To Reduce the Risk of Fire or Electric Shock Use only Class 2 sources Suitable for Interconnection Use Copper Conductor Only Select an external power supply that is certified for safety fo...

Страница 15: ...000 3 2 1999 Power Line Harmonics Class D EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Immunity Level B EN...

Отзывы: