Delta Controls DLC-G1212 Скачать руководство пользователя страница 2

Delta Lighting Controller (GE Lighting) DLC-G1212 (Rev 1.3) Installation & Application Guide

 

Model Numbers 

 
The GE Lighting Controller has the following product number: 

DLC-G1212

 

 

Accessories 

 

• 

TRM-768 

Delta Network Terminator for MS/TP 

• 

RPT-768 

Delta Network Repeater for MS/TP 

• 

475000-475032    12,24 and 48 Relay Capacity GE Lighting Panels (Delta Peripherals Catalog) 

• 

475100          GE Isolated Pilot Contact 5-wire relay with 5 pin connector (Catalog # RR9P) 

• 

475101          GE Standard 3-wire relay with 5 pin connector (Catalog # RR7P) 

 
 

Package Contents 

 

• 

Delta Lighting Controller

 (GE Lighting) Board, 

DLC-G1212 (Rev 1.3)

 

• 

DLC-G1212 (Rev 1.3)

 Installation Guide 

 
 

Other Relevant Documents 

 

• 

Delta Controls Wiring Guidelines 

• 

ORCAview Operator Guide 

• 

ORCAview Technical Reference Manual (particularly Appendix G in the 

V3.22 Tech. Ref. Manual

• 

Release Notes for V3.22 Firmware/Software 

 
 

Important Information 

 
The capabilities of the GE Lighting Controller are dependent on the firmware version that is loaded.  The 
following is not intended to be comprehensive, but should provide a quick overview. 

1.  V3.22 Firmware & Software or Higher (Recommended) 

CONTROLLER CAPABILITIES & CHARACTERISTICS 

• 

Unlike some other products, the DLC-G1212 is pre-configured as a Subnet device 

• 

A DCU is no longer necessary (as long as one System device exists on a BACnet MS/TP network) 

• 

Data exchange may be done in GCL programming in any DCU or Application Controller on a 
BACnet MS/TP network 

• 

Now Supported: Peer Data Exchange, Alarms, Routing, Slave Devices, Additional Objects 

Refer to 

V3.22 DAC Firmware Release Notes

 for further information. 

2.  V3.21 Firmware & Software 

CONTROLLER CAPABILITIES & CHARACTERISTICS 

• 

The DLC-G1212 was not tested with V3.21 firmware.  If loaded with V3.21 it would have similar 
capabilities and limitations as other DAC products with V3.21 firmware. 

 

 

Page 2 of 15

 

 

Document Edition 1.5

 

Содержание DLC-G1212

Страница 1: ...ching up to 12 GE lighting relay zones the GE Lighting Controller is ideal for mounting in various GE relay enclosures for both new and retrofit construction projects The controller also includes a bu...

Страница 2: ...3 22 Firmware Software Important Information The capabilities of the GE Lighting Controller are dependent on the firmware version that is loaded The following is not intended to be comprehensive but s...

Страница 3: ...ing Relay Outputs Maximum 4 GE Relays per output RR7x 3 wire Relays Control Only with No Status Delta PN 47101 Relays with no feedback RR9x 5 wire Relays Control and Status including LED Indication De...

Страница 4: ...d jumpers or Software Setup DIP switch MAC Address Range 0 to 99 per network segment Software Address Range As per the BACnet standard Supports DNA Delta s intuitive addressing scheme Size Controller...

Страница 5: ...E L 9 R E L 1 0 SWITCH 9 SWITCH 10 R E L 1 1 R E L 1 2 SWITCH 11 SWITCH 12 SC AN P W R RS O N OF F G ND RS O N OF F G ND RS O N OF F G ND RS O N OF F G ND RS O N OF F G ND RS O N OF F G ND RS O N OF...

Страница 6: ...ing data through the port Inputs IP1 IP12 Input Status Indicators A corresponding red LED flickers when the associated binary input is in the active state Sweep Output OP13 Sweep Output Signal Indicat...

Страница 7: ...mapped into the Subnet portion of its address inheriting other portions of its BACnet address when DNA is enabled DNA DERIVED NETWORK ADDRESSING DNA Derived Network Addressing DNA which works in conj...

Страница 8: ...ON OFF GND POWER OUT GND BI1 SWITCH 3 RELAY 2 SWITCH 2 RELAY 3 RELAY 4 SWITCH 4 SWITCH 5 SCAN PWR RS ON OFF GND RS ON OFF GND RS ON OFF GND PILOT ON OFF GND FRONT VIEW BACK VIEW GE RS3xP LOW VOLTAGE...

Страница 9: ...ropagation of 66 or higher Topology Ensure the MS TP network cable is installed as a daisy chain from one device to the next Max Nodes The maximum number of devices per MS TP network without any repea...

Страница 10: ...ext 1000 or 300m maximum 3 Ensure you install MS TP terminator boards when you have more than 1 or 2 devices 4 Depending on the controller up to 12 devices are supported on a LINKnet network with limi...

Страница 11: ...ed to represent two things Relay Output i e command Relay Status including when controlled by associated hardwired lighting switches E g To look for the Status Feedback Value the property you should u...

Страница 12: ...BO object to a non feedback condition To set the Binary Output BO object to a non feedback condition 1 Open the BO associated with the RR7 relay 2 Under the Device Tab in the Module section there is a...

Страница 13: ...CC Compliance Information This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reas...

Страница 14: ...erconnected To Reduce the Risk of Fire or Electric Shock Use only Class 2 sources Suitable for Interconnection Use Copper Conductor Only Select an external power supply that is certified for safety fo...

Страница 15: ...000 3 2 1999 Power Line Harmonics Class D EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Immunity Level B EN...