English

Installation of the outdoor unit drain line (if available)

During operation in the heating mode, the condensate water
may be drained from the outdoor unit through three drain
holes.

Insert the drain male fitting into the hole where drainage of
the condensate water is required and plug the remaining
two holes using the plugs B supplied in the kit, as shown in
Fig.(14).

FLOOR INSTALLATION

Installation on a floor or flat roof does not necessitate fixing
the feet to the floor. The feet should instead be placed on
supports (~70÷80 mm) to allow application of the conden-
sate drain line (for units with heat pump only).

The minimum distances shown in the figure should be
observed. Fig.(15).

SUSPENDED INSTALLATION

The minimum spaces indicated should be observed for
suspended installation, which requires a support kit that
must be ordered separately.

Carefully check the structure and the capacity load of
the supporting wall. Fig.(16).

Fig. 14

Fig. 15

Fig. 16

100 mm

200 mm

100 mm

100 mm

A

B

C

D

INSTALLATION OF THE OUTOOR UNIT

I

Содержание CF-CP 30 ARE 290

Страница 1: ...aordinary maintenance 35 User diagnostics 36 U I A U I A U I A 70 C A I U The following symbols have been used in some parts of this booklet and inside the appliance User Installer After sales service...

Страница 2: ...cubic metres The CP30 CF30 ARE 290 air conditioner must be used and stored in rooms with a volume of over 53 cubic metres The CF40 ARE 290 air conditioner must be used and stored in rooms with a volu...

Страница 3: ...r suitable absorbent material Prevent the liquid from entering into drains sewers cellars or work holes since the vapors could create a suffocating atmosphere First aid measures Inhalation Remove the...

Страница 4: ...ove the packing only when the air conditioner has been located in the point of installation Carefully remove the adhesive strips positioned on the air conditioner Packaging components must be disposed...

Страница 5: ...ONNECTION OFTHE UNIT I QUICK CONNECTOR I BASIC OPERATION The fast connector coupling uses a retractable sleeve and stem valve on the female half and a spring loaded poppet on the male side to create a...

Страница 6: ...he handle bottoms on the coupling body and the locking pin on models equipped with spring loaded locking pins pops into the handle hole properly see Figure 4 Connect the auxiliary electrical and conde...

Страница 7: ...couplings connected even when the system is not in use in order to minimize refrigerant effusion coupling damage and the entry of dirt or other foreign material If it is not possible to keep the coup...

Страница 8: ...a micropro cessor card 1 Wall mounting plate 2 Indoor unit base 3 Indoor fan motor 4 Sensor unit 5 Room sensor support 6 Card support box 7 Noise filter 8 Fan capacitor transformer 9 Electronic card 1...

Страница 9: ...is commanded and controlled by an electronic microprocessor system 100 Right handle 101 Left handle 102 Filter 103 Fan breakaway starting capaci tor 104 Compressor 105 Compressor cap 106 Compr protec...

Страница 10: ...AX Cooling 21 C d b 16 C w b 32 C d b 23 C w b 10 C d b 43 C d b Heating 15 C d b 27 C d b 10 C w b 18 C w b Performance is referred to the following conditions Cooling indoor unit inlet air temperatu...

Страница 11: ...ply connector XS2 XP2 Motor M1 power supply connector XS3 Quick connector XT1 Power supply terminal board A I A I FLAPS ID1 ID2 12VAC SW IR HALL ST2 ST1 BLACK WHITE RED BLUE PINK YELLOW ORANGE RED 123...

Страница 12: ...alve INDOOR OUTDOOR UNIT WIRING DIAGRAMS OUTDOOR UNIT MULTIFILAR WIRING DIAGRAM A I A I XS1 XT2 YB1 M1 C1 C FR1 Z1 R S C2 M 4 2 1 3 5 6 XS1 XT2 M1 C1 C FR1 Z1 R S C2 M 4 2 1 3 5 6 YB1 M1 XT2 C1 C2 FR1...

Страница 13: ...indoor and the outdoor unit taking into consideration the minimum technical spaces maximum length of the refrige rant lines and the difference in level between the applian ces The indoor unit should b...

Страница 14: ...screws provided in the kit To facilitate dril ling operations it is advisable to fix the unit onto the fixing plate lift the front part and mark the drilling points on the wall through the relative h...

Страница 15: ...a floor or flat roof does not necessitate fixing the feet to the floor The feet should instead be placed on supports 70 80 mm to allow application of the conden sate drain line for units with heat pum...

Страница 16: ...t the conden sate is flowing out regularly The drainage pipe should have a 2 slope down towards the drain it should never slope upwards Check all the joints for leaks Apply thermal insulating material...

Страница 17: ...not spray insecticide or similar products on the unit CLEANING THE AIR FILTERS To ensure the long life and efficiency of your air conditioner follow these instructions 1 Clean the dust filter once a w...

Страница 18: ...to on Check Faulty electronic card PROBLEM CAUSE REMEDY Insufficient output Check see user booklet General failure Simultaneous blinking of indi cator lights Just wait 3 and the air conditioner will...