INSTALLER CONNECTIONS
U I A
Boiler control
A) REPLACEMENT:
the boiler is only enabled if the outside
air temperature is less than the value of parameter 0307
and the compressor is off, figure 3.
To enable boiler activation in REPLACEMENT mode set
parameter 0306=1 and 010H = 1
Boiler operation reflects the trend in water temperature, as
shown on the graph in figure 4.
If the heat pump shuts down due to an alarm the boiler is
activated automatically regardless of the outside air temper-
ature.
In REPLACEMENT mode the activation delay time is
ignored, and the boiler is activated immediately if necessary.
Description
Enable electric heater
0 = Heater not enabled
1 = Heater enabled
Activation Boiler
0 = Boiler not enabled
1 = Boiler enabled
Type of boiler operation
0 = Supplementary
1 = Replacemen
Activation with low outside air
temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable
boiler
Integration time to activate boiler
Menu
Mn03
Mn03
Mn01
Mn03
Mn03
Mn06
Parameter
no.
0300
0301
010H
0306
0307
0619
Value to be
set
0
1
1
1
Example
-5°C
600
UOM
°C
°C*sec
B) SUPPLEMENTARY:
the boiler operates in supplemen-
tary heating mode, together with the compressor, to satisfy
the heating load.
Supplementary heating for low outside air temperature
The boiler is enabled only when the outside air temperature
is less than the value of parameter 0307, figure 3.
To enable the supplementary heating for outside air temper-
ature set parameter 0306 = 1 and 010H = 0
Boiler operation reflects the trend in water temperature, as
shown on the graph in figure 4.
Description
Enable electric heater
0 = Heater not enabled
1 = Heater enabled
Activation Boiler
0 = Boiler not enabled
1 = Boiler enabled
Type of boiler operation
0 = Supplementary
1 = Replacemen
Activation with low outside air
temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable
boiler
Minimum outside air temperature
for heat pump operation (make
sure the value set is the same as
shown in the table)
Boiler activation delay time (allows
the heat pump to reach steady
operation and thus avoid activat-
ing the boiler when not needed)
Integration time to activate boiler
Menu
Mn03
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no.
0300
0301
010H
0306
0307
0311
0618
0619
Value to be
set
0
1
0
1
Example
-5°C
-15
60
600
UOM
°C
°C
min.
°C*sec
Boiler operating parameters in REPLACEMENT mode
Boiler operating parameters in SUPPLEMENTARY mode
for outside temperature
Boiler
43 44
BT9
6
7
BT9
Boiler
43 44
6
7
1
2
Set the parameters following the sequence described in
the table
Set the parameters following the sequence described in
the table
KM2 Boiler
A boiler can be used as a supplementary or replacement
heat source for the system.
Solution 1
System with heat pump and boiler with storage tank.
Solution 2
System with heat pump and boiler without storage tank.