SYSTEM CONFIGURATION
U I A
Parameter configuration
Description
Menu
Parameter
no.
Default
Write
set value
UOM
SYSTEM compensation curves in heating mode
Enable SYSTEM compensation curve
0= Disabled
1= Enabled
Mn01
0152
0
-
SYSTEM compensation curve number
Mn01
0159
1
-
Enable room temperature influence on SYSTEM
0= Disabled
1= Enabled
Mn01
0163
0
-
SYSTEM Room Authority
Mn01
0164
30
%
MINIMUM return set point limit for SYSTEM curve
Mn01
0165
30
°C
MAXIMUM return set point limit for SYSTEM curve
Mn01
0166
48
°C
SYSTEM compensation curves in cooling mode
Enable SYSTEM compensation curve
0= Disabled
1= Enabled
Mn01
0154
0
-
Maximum return temperature set point limit in cooling mode (Tm1)
Mn01
0128
25
°C
Minimum outside temperature corresponding to max. return
temperature (Te1)
Mn01
0129
23
°C
Minimum return temperature set point limit in cooling mode (Tm2)
Mn01
0130
23
°C
Maximum outside temperature corresponding to min. return
temperature (Te2)
Mn01
0131
36
°C