60
AWR-MTD2-XE
EN 11/2010
MAINTENANCE AND SERVICE
A
ALARM TABLE
Alarm code
Cause
Solution
A001
BT1 System heat exchanger water inlet temperature probe
Probe faulty or disconnected
A002
BT2 System heat exchanger water outlet temperature probe
Probe faulty or disconnected
A003
BT8 DHW storage temperature probe
Probe faulty or disconnected
A004
BT7 Outside air temperature probe for unit management
Probe faulty or disconnected
A005
BT9 Storage tank temperature probe
Probe faulty or disconnected
A006
BT11 Outside air temperature probe
Probe faulty or disconnected
A007
BP1 High pressure transducer
Transducer faulty or disconnected
A013
F1 High pressure switch
Check connection
Check refrigerant circuit pressure
A014
High pressure measured by transducer BP1
A019
Difference between low and high pressure in refrigerant circuit too low
Check refrigerant circuit pressure
Check refrigerant charge
A022
Operation outside of limits
Make sure outside air temperature and water tempera-
ture set point are inside the specified operating limits
A023
Source differential pressure switch/flow switch activated
Make sure the filter is clean
Make sure the system is filled with water
Check water flow-rate
A025
Differential pressure switch / system flow switch F3 activated
Make sure filters are clean
Check water flow
Check for air in the system
A030
Compressor operating hours reached
Scheduled maintenance
A033
System pump operating hours reached
Scheduled maintenance
A034
Domestic hot water pump operating hours reached
Scheduled maintenance
A035
Mixed zone pump operating hours reached
Scheduled maintenance
A036
Fan operating hours reached
Scheduled maintenance
A038
System heat exchanger frost prevention alarm
Scheduled maintenance
A041
DHW storage temperature too high
A042
Inside frost prevention alarm
A045
Outside air temperature probe
Check connections
Faulty probes, replace terminal
A047
Thermostatic valve driver
Contact service centre
A048
A049
A050
A051
A052
A053
A054
Legionella prevention alarm
A055
Temperature probe N-THC n.1
Check connections
Probe faulty or disconnected
A056
Address setting error on remote terminal supplied with the unit
Check connections
Check address
A057
Address setting error on expansion module 2
Check connections
Check address, must be 1
A058
Temperature probe in low temperature zone LT2, expansion 2
Probe faulty or disconnected
A063
Address setting error on expansion module 3
Check connections
Check address, must be 2
A064
Temperature probe in low temperature zone LT3, expansion 3
Probe faulty or disconnected
A075
Water temperature too high in mixed circuit, expansion module 1
A077
Water temperature too high in mixed circuit, expansion module 2
A094
End defrost due to maximum time
A095
Temperature probe N-THC n.2
Check connections
Probe faulty or disconnected
A096
Address setting error on zone remote terminal
Check connections
Check address
A097
Temperature probe N-THC n.3
Check connections
Probe faulty or disconnected
A098
Address setting error on zone remote terminal
Check connections
Check address
A099
Temperature probe N-THC n.4
Check connections
Probe faulty or disconnected
A100
Address setting error on zone remote terminal
Check connections
Check address
A101
Temperature probe N-THC n.5
Check connections
Probe faulty or disconnected
A102
Address setting error on zone remote terminal
Check connections
Check address
A103
Address setting error on expansion module 1
Check connections
Check address, must be 1
A104
Low temperature zone LT1 temperature probe, expansion 1
Probe faulty or disconnected
A109
Low pressure alarm from low pressure switch
Check connection
Check refrigerant circuit pressure
A114
Solar/pool module address setting error
Check connections
Check address
A115
Solar/pool module general alarm
A116
Master unit not connected, cascade control
A117
Slave unit not connected, cascade control
A120
Water temperature too high in mixed circuit, expansion module, expansion module 3
A121
Temperature probe N-THC n.6
Check connections
Probe faulty or disconnected
A122
Address setting error on zone LT3 remote terminal
Check connections
Check address