Figure 126. Locking the DIB into place
3. Replace the Access Module as described in
Verify the operation of a replacement DIB
Steps
1. From PowerStore Manager, select
Hardware
.
2. Select the appliance where you replaced the DIB.
3. On the
Components
card, under
Rear View
, expand
ExpansionEnclosure
.
4. Select the relevant
DIB
.
The status of the replacement DIB should read
Healthy
. If the status is still
Faulted
, wait a few minutes and refresh
PowerStore Manager. If the status does not change, ensure that the DIB is correctly seated, or contact your service
provider.
Return a faulted part
About this task
For US customers, return defective material within five business days. For International customers, return defective material
within 10 business days. The materials required to return your defective part are supplied with the good part shipment.
Steps
1. Package the faulted part in the shipping box that contained the replacement part.
2. Ship the failed part to your service provider as described in the instructions that were included with the replacement part.
3. For more information about returning customer-replaceable parts:
a. Open PowerStore Manager.
NVMe expansion enclosure service procedures
109
Содержание PowerStore 500T
Страница 33: ...Figure 29 Cabling two expansion enclosures Install a new base enclosure and optional expansion enclosure 33 ...
Страница 37: ...CL5262 Figure 33 Installing the bezel Install a new base enclosure and optional expansion enclosure 37 ...
Страница 97: ...Figure 113 Installing a fan module 2 Close the system cover NVMe expansion enclosure service procedures 97 ...