Replace the system board
Complete the following procedure to replace the system board.
This FRU is not hot-swappable, and requires a system shutdown to replace.
After a system board replacement, user-configured iDRAC settings and users are reset. Those settings must be reconfigured
manually.
CAUTION:
Do not move the TPM from the old system board to the new system board. A new TPM is included
with the replacement system board.
Topics:
•
Verify the status of the system board
•
Shut down and disconnect the system
•
•
Extend the system from the cabinet
•
•
•
Remove the cooling fan assembly
•
•
Remove the integrated storage controller card
•
•
Remove processor and heat sink module
•
•
•
Install a processor and heat sink module
•
•
Install the integrated storage controller card
•
Install expansion card riser 1
•
Install expansion card riser 2
•
Install expansion card riser 3
•
Install the cooling fan assembly
•
•
•
•
Slide the system into the cabinet
•
Reconnect and power on the system
•
Restoring the Service Tag by using the Easy Restore feature
•
Enter the system Service Tag by using System Setup
•
•
Upgrade the identity module firmware
•
Bring up the existing file system
•
Verify the status of the system board
Prerequisites
Establish a connection to the system as described in
Establish a serial management connection to the PowerProtect system
page 14.
13
Replace the system board
105