9
Safety Warnings
|
Safety Warnings
CAUTION:
Before performing the procedures in this document, read and follow the safety instructions and
important regulatory information in your
Safety, Environmental, and Regulatory Information
document.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment and
save this manual for future reference.
DANGER:
Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S
This UPS contains
LETHAL VOLTAGES
. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY
. There are
NO USER SERVICEABLE
PARTS
inside the UPS.
WARNING:
Observe the following instructions to help prevent a potentially hazardous situation which, if not
avoided, could result in death or injury:
S
This UPS contains its own energy source (batteries). The output receptacles may carry live voltage
even when the UPS is not connected to an AC supply.
S
Do not remove or unplug the input cord when the UPS is turned on. This removes the safety
ground from the UPS and the equipment connected to the UPS.
S
To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent
protection with an ampere rating in accordance with the National Electrical Code
®
(NEC
®
),
ANSI/NFPA 70 or your local electrical code:
UPS Output Power
120V
208V
230V
2700W
30A
20A
16A
S
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 40
°
C (104
°
F). Do not operate near water or excessive humidity (95% maximum).
S
Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and
on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely
dry (hazard of electric shock).
S
If the UPS requires any type of transportation, disconnect the internal UPS batteries before
transporting (see page 58).