64
|
Specifications
Table 13. Electrical Output
120V Models
208V Models
230V Models
Power Levels
(rated at nominal inputs)
2700W
Regulation (Normal mode)
-6% to +6% of nominal voltage
NOTE:
This varies based on auto-detected input voltage or customer settings.
Regulation (Battery mode),
Nominal Voltage ±5%
-6% to +6% of nominal voltage
NOTE:
This varies based on auto-detected input voltage or customer settings.
Voltage Waveform
Sine wave
Output Receptacles
(1) L5-20R, 20A
(2) 5-20R, 20A
(2) IEC 320-C13, 15A
(1) L6-20R, 20A
(2) L6-30R, 30A
(6) IEC 320-C13, 10A
(1) IEC 320-C19, 16A
(2) IEC 320-C13, 10A
Table 14. Environmental and Safety
120V Models
208V Models
230V Models
Operating Temperature
Up to 1,500 meters: 0°C to 40°C (32°F to 104°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Transit/Storage
Temperature
-15°C to 60°C (5°F to 140°F)
Relative Humidity
0–95% noncondensing
Operating Altitude
Up to 3,048 meters (0–10,000 ft) above sea level
Audible Noise
Less than 55 dBA on line/bypass mode (less than 75% load), room temperature
Fan Speed
Off: when the UPS is in Standby mode or there is no load
Low speed: when the load is < 80%
High speed: when the load is >80% or the UPS is in Battery mode
Surge Suppression
ANSI/IEEE C62.41; 2002 Category B
Safety Conformance
UL 1778 4th Edition;
CSA C22.2, No. 107.3
UL 1778 4th Edition;
CSA C22.2, No. 107.3;
IEC/EN 62040-1-1;
IEC/EN 60950-1
Agency Markings
UL, cUL, NOM/NYCE
UL, cUL
UL, cUL, CE, GS, GOST,
BSMI, S-MARK, KC,
CQC, NRCS, SIRIM
EMC (Class A)
FCC, ICES-003
FCC, ICES-003, VCCI
CE, BSMI, CQC, C-tick