Page 2
935 SOUTH WOODLAND AVENUE, MICHIGAN CITY, IN 46360-5672
TEL.: 219-861-0661 - FAX: 219-861-0662 - TOLL-FREE: 888-925-5444
www.dekkervacuum.com
DEKKER CONTROLLER OVERVIEW
Dekker’s Controller is standard on the Vmax models. The Dekker Controller provides for system control
as well as monitoring of system status. Service functions include display of spare parts list, maintenance
schedules, and service history, along with logging of fault conditions.
The Dekker Controller includes a 4-line large-font liquid crystal display, a durable Lexan membrane
keypad, and multiple status LEDs. Communication between controllers is via RS-485 for multi-machine
systems. An Ethernet port provides for remote monitoring and control via TCP/IP protocols and can be
enhanced with the use of Dekker’s OnDek Software (optional and purchased separately). Input and
output (I/O) includes 9 digital (24VDC) inputs and 7 dry relay contact outputs. Analog I/O includes 2 RTD
(Resistance Temperature Detectors) inputs, four 0-10VDC/4-20mA inputs, one 0-10VDC output, and one
4-20mA output. Power input to the controller is 24VDC.
DEKKER CONTROLLER KEYPAD
The Dekker Controller text display, buttons, and LEDs are described below. Refer to the diagram below
that shows this information.
4 line LCD Display
ESCAPE BUTTON RETURNS TO
RUN/STANDBY/STOPPED SCREEN
PROGRAM BUTTON PROGRAM MENU
FOR SETPOINTS, CLOCK, UNITS
MAINT BUTTON MENU FOR: SPARE
PARTS LIST MAINTENANCE SCHEDULES
SERVICE HISTORY
LOG BUTTON FAULT HISTORY LOG
MENU
RESET BUTTON RESETS FAULTS
RUN STATUS LED GREEN = SYSTEM
RUNNING ORANGE = STANDBY/AUTO
MODE RED = SYSTEM STOPPED
OFF LED RED = SYSTEM STOPPED
OFF BUTTON STOPS SYSTEM
ON BUTTON STARTS SYSTEM
GREEN= SYSTEM RUNNING
OR IN STANDBY
POWER ON BUTTON
TURNS CONTROLLER ON
AND OFF
POWER ON LED
RED=CONTROLLER
R
POWER ON
HAND/AUTO
BUTTON
ALTERNATES
BETWEEN
HAND AND
AUTO
MODES
HAND/AUTO
LED
ORANGE=HAND
GREEN=AUTO
ENTER
BUTTON
SELECT
MENU ITEMS
MENUS AND
VALUES
UP / DOWN – ARROW/ - BUTTON
NAVIGATE MENUS AND CHANGE