Scavenger Output
Output 6 on the controller is used for a bleed valve. This output cycles on for 30 Secs and off for 9
minutes based on vacuum level. The vacuum level for cycling to occur is adjustable via the Setpoint
menu on the Dekker Controller.
Enter password
Press PROG until Setpoints screen is shown.
Using DOWN arrow scrool to Scav Lvl
Press ENTER
Use UP/DOWN arrows to change value
Press ENTER to save.
ENTER